5. OPERATION

Note:
The entire operation of the control system must only be
carried out by qualified expert personnel.
The user can set the humidity set points in the pro-
gramme CtrL if necessary, see page 17.

5.1. CONTROL UNIT

3
4
5
2
1
1 On/off switch
2 Display
3 LED corresponding to the SELECT button
The LED flashes when the SELECT button must be
pressed.
4 SELECT button
You can choose between different functions in a pro-
gramme.
5 LED corresponding to the SET button
The LED flashes when the SET button must be pressed.
6 SET button
Values can be set.
7 DIP switch
The DIP switches are already correctly set as default and
must not be moved.
8 MODE button
• Manually rinse steam cylinder
• Start programmes
6
7
8
M+P-26A-1019

5.2. PROGRAMMES

The following programmes can be started using the MODE
button:
• dISP (display)
Basic function of the display.
Note:
The display is already set to 40 % for the relative hu-
midity as default.
• SEr (service)
Functions for the service.
• AdJ (Adjustments)
Set parameters.
• CtrL (controller)
Enable internal humidity controller.
Set parameters.
• drA (drain)
Set special drain functions.
• Coun (count)
Display operating hours.
• rSt (reset)
Reset settings to factory settings.
• inFo (information)
Display software version.
5.2.1.

"Service" programme

The following functions can be started using the SEr pro-
gramme:
• Display water level in the steam cylinder.
• Display steam request.
• Effective heating current in amperes.
• Manually confirm the components of the humidifier for a
service check.
1. Repeatedly press MODE button until the display shows
SEr.
2. Press SELECT button.
SE.on is displayed when the maximum water level is
reached.
SE.oF is displayed when the maximum water level is
not yet reached.
3. Press SELECT button.
H on is displayed when steam has been requested.
H oF displayed when no steam has been requested.
4. Press SELECT button.
0000 displays the effective heating current in amperes.