3. Specifications
Overload safety
The overload safety is based on the sensor element used. Depending on the selected process connec-
tion and sealing, restrictions in overload safety can result.
EN
A higher overload safety will result in a higher temperature error.
Measuring ranges ≤ 25 bar [≤ 400 psi]: 3-fold
Measuring ranges 40 ... 600 bar [500 ... 5,000 psi]: 2-fold
Measuring range 1,000 bar: 1.5-fold
1) 1.5-fold overload safety with 1,000 psi, 1,500 psi and 10,000 psi
Vacuum resistance
yes
3.2 Output signal
Signal type
Current (2-wire)
Current (3-wire)
Voltage (3-wire)
USB
CANopen
Load in Ω
Current (2-wire, 3-wire):
Voltage (3-wire):
10
Signal
4 ... 20 mA
4 ... 20 mA
0 ... 20 mA
DC 0 ... 10 V
DC 0 ... 5 V
per P-30/P-31 interface protocol
per CiA DS404
≤ (power supply - 9 V)/0.02 A
> U
/1 mA
max
WIKA operating instructions pressure transmitter, model P-3x
1)