Mode of switching:
Integral, direct, circular or linear.
Saving-function:
All programmed parameters and
modes are saved in a non-volatile
memory.
Power outage release:
Quick automatic disconnection in
less than 20ms (50Hz) in case of
power outage or voltage drop.
Power outage reset delay time:
40s.
Overvoltage and undervoltage
protection.
Autoadaptation to the phase-ro-
tation of the network and the CT-
terminals.
Not affected by the harmonics.
Working with generative and re-
generative loads.
LCD contrast automatically com-
pensated with temperature.
Operating temperature:
-10°C to 70°C.
Storage temperature:
-30°C to 85°C.
Mounting position:
Vertical panel mounting.
Dimensions:
144x144x43 mm (hxwxd).
Weight:
0.4 kg (unpacked).
Connector:
Spring clamp terminal block, max
2.5 mm².
Front plate protection:
IP 43.
Relative humidity:
Maximum 95%; non-condensing.
CE Marked.
13