Setting The Set Point; Disassembly And Exchange - Aventics ED05 Rail Notice D'instruction

Régulateur de pression
Masquer les pouces Voir aussi pour ED05 Rail:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

AVENTICS | ED05 | R414010201–BAL–001–AA | English

Setting the set point

O Stipulate the desired set point with the controller.
Control
You can continually adjust the pressure once you have
connected the pneumatic and electrical supply on the
ED05 pressure regulator. To do this, the ED05 pressure
regulator is controlled via a controller using a set point.
The electronics compare the set point with the outlet
pressure, which is measured by a pressure sensor, and
generate a control variable that is used to control the 3/3
directional valve with U/I converters and a proportional
solenoid. This sets the stipulated pressure.
Function block diagram for a ED05 pressure regulator
See Fig.
5
Selecting the correct supply pressure
A permanent deviation will occur if the supply pressure is
less than the outlet pressure stipulated by the electrical
set point. The electronics will reduce the power
consumption and thus the max. nominal width to prevent
the ED05 pressure regulator from heating up.
O Always select a supply pressure that is higher than the
outlet pressure.
Danger of burns caused by hot coils
Touching the valve coils during operating may lead to
burns.
O Let the device cool off before disassembling it.
O Do not touch the device during operation.
Displays
1
The ED05 pressure regulator has two LEDs:
W
Green LED "POWER" (9)
W
Red LED "STATUS" (8)
CAUTION
Meaning of the "POWER" LED
LED status
Meaning
LED is off
The supply voltage is less than 8 V.
Flashes
The supply voltage is less than 14.4 V,
(frequency
the standard function is switched off.
approx.
The adjusted pressure is 0 bar.
0.5 Hz)
Flashes
The supply voltage is less than 16.8 V,
(frequency
the device operates with reduced
approx.
performance.
1 Hz)
Flashes
The supply voltage is larger than 33.6 V
(frequency
and larger than the permitted range.
approx.
The device operates with reduced
20 Hz)
performance.
LED is
Device is ready for operation.
illuminated
Full performance in the supply voltage
range from 16.8 V ... 33.6 V.
Meaning of the LED "STATUS"
LED status
Meaning
LED is off
The device operates correctly.
Flashes
Error during the self-test , the device
does not function.
If the green "POWER" LED (9) is illuminated and the red
"STATUS" LED (8) is not illuminated, the ED05 pressure
regulator is operating correctly and the supply voltage is
within the tolerance range.
8

Disassembly and Exchange

Disconnecting plugs when under voltage will damage
the device
Large differences in potential occur when disconnecting
plugs under voltage, which could damage the device.
O Make sure the relevant system component is not
under voltage before disassembling the device.
1
1
NOTICE