For venting vertically into a Class A chimney, a
single wall pipe (at least 24 gauge) may be used in
E.
the room where the stove is installed. Refer to the
manufacturer's instructions for the connection to the
listed chimney. The chimney/stove pipe must not be
smaller than 6" (15cm) in diameter.
For venting directly into a masonry chimney or
through a thimble, the top of the single wall pipe
must be at least 18" (46cm) below a combustible
ceiling and must conform to NFPA 211 guidelines
and methods. Please see the diagram to the left.
Connector Pipe
18" (46cm) below ceiling
Min.
2" (5cm)
Insulated
Chimney
Min.
2" (5cm)
VIVA L USA - US English
A. Chimney Cap
B. Insulated Chimney
C. Storm Collar
D. Roof Flashing
E. Ceiling Support Box or Joist Shield/Firestop
Spacer
F. Chimney Connector
For rear venting or other unlisted configu-
rations, consult the local building codes
and follow the NFPA 211 guidelines.
If the stovepipe is fitted with a baffle, it
must be manually operated, visibly placed
for ease of use, and must not close com-
pletely. Consult your chimney expert if you
have any questions.
Important note:
Please ensure that there is easy access to
the chimney cleanout door.