Fig. 29: VARIPACK configuration "Pressure control"
No.
Fault
1
Overvoltage
2
Under-voltage
3
Overcurrent
4
Power stack fault
5
Power stack overcurrent
6
Current limit
7
Motor stall
8
Overload
9
Overload (permanent magnet motors)
10
Overcurrent at low speed
11
Ambient overtemperature heat sink
12
Ambient overtemperature control module
14
Compressor start failed
20
Line contactor
21
Phase failure
22
VDC ripple
24
24 V overload
27
STO active
29
Fan error
40
9 Fault messages and monitoring functions
Description of the fault types:
"Timed resets":
• "Timed reset" faults are reset automatically up to 5
times. If the fault is no longer active and the following
parametrised time delay has elapsed, the com-
pressor can restart. The "Timed Reset" interval can
be configured from VARIPACK firmware V1.14. The
factory setting is – like in the previous version –
300 s. Shorter intervals should only be set in sys-
tems equipped with a system controller with alarm
management function. After 5 errors within 5 con-
figured and successively elapsed intervals or after
5 errors within 5 minutes, an "External resets" error
is triggered.
• After an error-free operation of at least 5 minutes or
after 5 configured intervals performed successively
without any faults, the number of possible "Timed re-
sets" is reset to 5. This is also done if a fault is reset
actively, for example via the DI5 digital input (Reset).
"External resets":
• Faults of the "External reset" type are reset if the
fault is no longer active and a reset command is re-
ceived. The reset command can be sent by pressing
the red key on the control panel or via the digital in-
put (DI5) or via Modbus.
Warning
X
X
X
X
Fault type
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"
"Timed reset"