Capacity Control Of The Compressor As A Function Of The Evaporation Pressure - Bitzer VARIPACK FD+6 Instructions De Service

Convertisseurs de fréquences
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

"0 .. Max" control characteristic
Alternatively, the "Min .. Max" control characteristic can
be switched to "0 .. Max" by a change in parameter.
• In the "0 .. Max" control characteristic, in addition to
the DI1 (X13: 2) start command, a setpoint signal of
> 1% (0.1 V) is required for starting the compressor.
f [Hz]
0 .. 10 V
f
max
f
min
0
0,1
2
4
1%
Fig. 13: "0 .. Max" control characteristic
5.4.2
Capacity control of the compressor as a
function of the evaporation pressure
To control the capacity of the compressor as a function
of the evaporation pressure will require the optional ex-
tension module for pressure control.
Installation of the extension module kit (part number
347 972 01):
• Plug the extension module into the top slot of the FI
control module and tighten the screw.
• Ratiometric pressure transmitter
– Install the pressure transmitter labelled
"2CP5-71-49" on the low pressure side.
– Install the pressure transmitter labelled
"2CP5-71-47" on the high pressure side.
– In the case of Schrader valves, install the pres-
sure transmitters without a copper gasket ring to
ensure safe opening.
For the wiring of the extension module, see chapter
Schematic wiring diagrams semi-hermetic reciprocating
compressors, page 26.
Function and technical data of the extension
module
• X1: 1, 2 and 3
CB-100-2
6
8
10
U [V]
The setpoint signal presets the frequency to a value
between 0 Hz and the maximum frequency. If the
signal is > 1% but lower than the minimum frequency
of the compressor, the compressor will run at the
minimum frequency.
Graphical explanation of the "0 .. Max" control charac-
teristic, see figure 13, page 21.
f [Hz]
4 .. 20 mA
f
max
f
min
12
0
4
4,16
1%
– Input for ratiometric low pressure transmitter.
– Correct function is indicated by blue LED.
• X1: 4, 5 and 6
– Input for ratiometric high-pressure transmitter
– Correct function is indicated by red LED.
• X2: 1
– Analogue output for transmitting the low-pressure
value to the FI (X11: 1: AI1).
• X2: 2
– Analogue output for transmitting the high-pressure
value to the FI (X11:2: AI2).
• X3: 1
– Input for 24 V DC power supply coming from the
FI (X12: 5).
• X3: 2, 3, 4, 5 and 6
– 24 V = outputs.
– Allow simple wiring of the digital inputs of the fre-
quency inverter.
• X4: 4
8
12
16
I [mA]
20
21