4 | Product description
2.3
Scope of delivery
4
Fig. 2
Scope of delivery
[1]
Module CZM100 (Comfort Zone Manager)
[2]
Supply temperature sensor (LLH)
[3]
Pouch with installation material and zone valve terminals
[4]
Installation Instructions, installation advice
2.4
Technical Data
Technical Data
Module Dimensions
(W × H × D)
Maximum cable type
• Connecting terminal, line-
voltage side
• Connecting terminal, low-
voltage side
Rated voltages
• BUS
• Power supply (at CZM100)
• Power Supply CRC100/
CRC200
• circulator pump terminals
• zone valve terminals
Fuse
• Connecting terminal, line-
voltage side
• Connecting terminal, low-
voltage side
BUS interface
Power draw – Standby
Table 4 Technical Data
6 720 811 731 (2015/01)
1
2
3
6 720 811 731-01.1O
9 11/16" × 5 15/16" × 2 13/32",
(246 × 184 × 61 mm, for additional
dimensions Figs. 3 and 4)
2
• AWG14 (2.5 mm
)
2
• AWG18 (0.75 mm
)
• 15 V DC (polarized)
• 120 V AC, 60 Hz
• 15 V DC (polarized)
• 120 V AC, 60 Hz
• 24 V AC
• 120 V, 5 AT
• 24 V, 5 AT
EMS
< 1 W
Technical Data
Maximum power output
• per connection(PZ1 ... PZ3)
• per connection(VZ1 ... VZ3)
Specified measuring range for
supply temperature sensor
• Lower error limit
• Display range
• Upper error limit
Permissible ambient
temperature
Protection
Protection class
Ident. No.
Certification
Table 4 Technical Data
2 27/32"
2 27/32"
(72 mm)
(72 mm)
9 11/16"
(246 mm)
Fig. 3
Dimensions – Front view
Fig. 4
Dimensions – Side view
• 120 V AC, max 2 A per contact,
in total 5 A
(high-efficiency pumps
permissible; max. 40 A/s)
• 24 V AC, max. 1.5 AT
• < 14 °F (< -10 °C)
• 32 – 212 °F (0 – 100 °C)
• > 257 °F (> 125 °C)
32 – 140 °F (0 – 60 °C)
IP 20
I
Data plate ( Fig. 5, page 5)
6 720 810 538-02.1O
2 13/32"
(61 mm)
6 720 810 538-102.1O
CZM100