Hazardous location
Cl I, DIV 1, GP A,B,C,D
Cl II, DIV 1, GP E,F,G
Cl III, DIV 1
Cl I, ZN 0,1 GP IIC
T6
@ T
= -40°C ... +55°C
a
T5 @ T = -40°C ... +70°C
a
T4 @ T = -40°C ... +85°C
a
Connection
head
see note 3
Entity parameters:
Terminals 1(+), 2(-):
U , V
= 30 VDC
i
max
I , I
= 100 mA
i
max
P , P
= 0.75 W
i
max
L
= 106 H
i
m
C
= 13 nF
i
Terminals 3, 4, 5, 6:
U ,
V ,
V
=
9.
6 VDC
o
oc
t
I I ,
,
I
= 7.6 mA
o
sc
t
P P
,
= 12.5 mW
o
t
L , L
= 290 mH
o
a
C , C
= 3.5 F
o
a
m
This document contains safety-relevant information based on technical standards
(i.e. Norms, internal standards) or certifications that the apparatus is subject to
and may only be altered with the approval of the norm expert (NFM)
Fab-Gr.:
Change No.:
Revision:
FK:
1
Date of change:
Modify by:
Change for:
see note 2
Temperature
Transmitter
TH100
_
+
1
2
3
6
4
5
PE
Notes:
1. The nonintrinsically safe terminals (power rail) must not be connected to any device
which uses or generates more than 250 Vrms or d.c. unless if has been determinated
that the voltage has been adequately isolated.
2. The installation must meet the requirements of the National Electrical Code /
Canadian Electrical Code
3. The SITRANS TH100 must be installed in a housing, e.g. Type B connection head
Tol.:
Date:
14.03.2006
Edited by:
Pi eta
Sudeta
Approved by:
A & D PD
Siemens d.d.
Non-hazardous location
(+)
(-)
For Intrinsic Safety
application use
approved associated
apparatus or barrier
Entity parameters:
V
or V
oc
I
or I
sc
P
or P
o
C > Sum (C ) + C
a
L
> Sum (L ) + L
a
Scale:
Engineering Obligation for Delivery
Product:
Temperature Transmitter

SITRANS TH100

Type 7NG3211-0B***
Title:
Control Drawing
for DIV 1, Zone 0,1
Document No.:
C10145-A3-X2-33
see note 1
30 VDC
t
100 mA
t
0.75 W
t
i
cable
i
cable
SAP No.:
Sheet
1
of
2
Doc. Type: