Coverage Patterns - LEGRAND Wattstopper PW-100-24 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Walk-Through
The Walk-Through mode shortens the time delay to reduce the amount of time the load is ON after a brief moment of occupancy, such
as returning to an office to pick up a forgotten item, then immediately exiting.
Walk-Through Mode
(DIP #4 ON)
No Walk-Through
DIP #4 OFF)
PIR Sensitivity Adjustment
The PW-100-24 constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions
that can cause false detections, while providing maximum coverage
High
(DIP #5 OFF)
Low, 50%
(DIP #5 ON)
Alerts
The PW-100-24 can provide audible and/or visible alerts as a warning before the load turns OFF.
Visible Alert
(DIP #6 ON)
No Visible Alerts
(DIP #6 OFF)
Audible Alerts
(DIP #7 ON)
No Audible Alerts
(DIP #7 OFF)

COVERAGE PATTERNS

Coverage testing has been performed according to the
NEMA WD 7 guideline. For best performance, use in spaces not larger than
15' x 12'.
PIR Sensor
The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree
field of view. The red LED on the sensor flashes when the PIR detects
motion.
Masking the lens
Opaque adhesive tape is supplied so that sections of the PIR sensor's view
can be masked. This allows you to eliminate coverage in unwanted areas.
Since masking removes bands of coverage, remember to take this into
account when troubleshooting coverage problems.
The PW sensor turns the load OFF three minutes after the area is initially occupied, if no motion is detected
after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay applies.
Walk-Through mode disabled.
Default setting. Suitable for most applications.
Reduces sensitivity by approximately 50%. Useful in cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and where heat sources cause unnecessary activation.
When only one minute is left in the time delay, the load connected to the relay turns OFF for one second.
This provides a one minute warning before the load(s) are turned OFF by the sensor.
No visible warnings provided.
Unit will beep at one minute, at 30 seconds and at 10 seconds before turning OFF load. When Walk-
Through is active, the unit beeps three times at 10 seconds before the load goes OFF.
*If Visible Alert is also ON, the one-minute time-out warning beep is replaced by the visible alert.
No audible warnings provided.
Top View
(10.6m)
4'
Side View
(1.2m)
2
Major motion
Minor motion
PIR
Coverage
35'
20'
(6.1m)
7.5'
(2.2m)
15'
(4.5m)
0
20'
(6.1m)
35'
(10.6m)

Publicité

Table des Matières
loading

Table des Matières