No: 24227 – 11/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: CX-100
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
CX-100-U is BAA and TAA compliant (Product produced in the U.S.)
The CX-100 is a 24VDC passive infrared (PIR) occupancy sensor which controls lighting and HVAC systems based on occupancy. It
also has a light level feature that can be used to keep sections of lights from turning on if the ambient light level is sufficient. The CX-100
contains an isolated relay with Normally Open and Normally Closed outputs for interfacing with HVAC or EMS.
PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them, so careful consideration must be given to sensor placement.
Coverages shown are maximum and represent coverage for walking motion. Actual coverage will vary slightly depending on mounting
height and furnishings.
Masking the lens: Opaque adhesive tape is supplied so that sections of the sensor's lens can be masked. This restricts the sensor's
view and allows you to eliminate coverage in unwanted areas.
Dense Wide Angle Lens (Standard)
up to 2000 sq ft for walking motion
up to 1000 sq ft for desktop motion
Two-Sided Aisleway Lens (-3)
up to 134 linear ft for walking motion
Wattstopper
PIR Occupancy Sensor with Light Level and Isolated Relay
Détecteur de Mouvement IRP avec contrôle du niveau de luminosité
et relais isolé
Sensor de Ocupación PIR con nivel de luz y relé aislado
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
UNIT DESCRIPTION
COVERAGE PATTERNS
®
SPECIFICATIONS
Voltage ................................................................. 24VDC
Current Consumption ............................................. 19mA*
Power Supply ............................ Wattstopper Power Pack
Isolated Relay Rating .................................... 1A@24VDC
Time Adjustment ........................ 15 seconds—30 minutes
Sensitivity Adjustment ..................... Minimum—Maximum
Light Level Adjustment ..................................... 3—200FC
*Current consumption can be slightly higher when only one
sensor per power pack is used.
Long Range Lens (-1)
up to 90 linear ft for walking motion
One-Sided Aisleway Lens (-4)
up to 50 linear ft for walking motion