Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: CI-24, CI-24-1
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
CI-24 models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
The CI-24 is a 24VAC or 24VDC Passive Infrared (PIR) occupancy sensor which integrates with HVAC or EMS systems. The CI-24
provides isolated relay contacts that are Normally Open or Normally Closed, based on occupancy.
PIR sensing systems are passive systems that react to changes in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them, so careful consideration must be given to sensor placement.
COVERAGE PATTERNS
The CI-24 has a multi-cell, multi-tier Fresnel lens
with a field of view of 360°. The sensor has two
lens pattern options. The Extended Range Lens will
cover up to 1200 sq ft when mounted at 8-12 feet.
The High Density/Reduced Range Lens will cover
up to 500 sq ft when mounted at 8-12 feet.
Coverage shown in the diagrams below is
maximum and represents coverage for half-step,
walking motion, with no barriers or obstacles.
NOTE: Drawings are not to scale.
Extended Range Lens (Standard) - CI-24
Side View
0
8' (2.4m)
10' (3m)
12' (3.7m)
40'
30'
20'
(12.2m)
(9.1m)
(6.1m)
The effective coverage distances may be slightly less than the maximum sensing distance (see
Coverage Patterns), depending upon obstacles such as furniture or partitions, and this must be
considered when planning the number of sensors and their positioning. See the list below for
approximate coverage distances for different types of motion.
Approximate Coverage, for a Mounting Height of 8 Feet:
Lens Option
Walking Motion
Extended Range up to 22 ft radius
(1200 sq ft)
High Density
up to 12 ft radius
(500 sq ft)
The CI-24 sensor can be mounted at various heights. When mounting at heights other than 12
feet, be aware that as you decrease the mounting height, you will decrease the range and increase the
sensitivity to smaller motions. Conversely, when you increase the height, you will increase the range
and decrease the sensitivity to smaller motions. At heights of more than 12-14 feet, you may start to
significantly reduce sensitivity.
Often the best location to install a CI- 24 in a closed office is off-center (see Fig.1). Avoid placing a sensor
directly in line with an open door in which it has a clear view out, as the sensor may detect people walking
by.
For open office areas with partitions, it is best to place sensors over intersections of four workstations
(see Fig. 2).
Also avoid placing the sensors close to air ducts, as rapid air currents or the differences in temperatures may cause false activations.
For large areas of coverage use multiple sensors.
DESCRIPTION AND OPERATION
10'
0
10'
20'
(3m)
(3m)
(6.1m)
Workstation
(Hand Motion)
12ft radius
(500 sq ft)
9ft radius
(300 sq ft)
Wattstopper
360° Passive Infrared Low Voltage Occupancy Sensor
IRP 360 ° Détecteur de présence de basse tension
Sensor de ocupación PIR de 360° de bajo voltaje
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage ................................................. 24VAC or 24VDC, ±10%
Current Consumption .................................. 60mA Max @24VAC
Isolated Relay Rating ............................... 1A @24VDC or 24VAC
Operating Temperature .........................32° to 131°F (0° to 55°C)
Time Delay Adjustment ...........................30 seconds–30 minutes
PIR Coverage
Sensitivity Adjustment ....................................Minimum/Maximum
UL & CUL Listed
CI-24
Top View @ 8ft
High Density/Reduced Range Lens CI-24-1
Side View
0
8' (2.4m)
10' (3m)
12' (3.7m)
30'
40'
20'
(9.1m)
(12.2m)
(6.1m)
PLACEMENT
®
SPECIFICATIONS
............................................................ 20mA Max @24VDC
Model CI-24 .......................................................up to 1200ft
Model CI-24-1 .....................................................up to 500ft
CI-24-1
Top View @ 8ft
15'
10'
5'
0
(4.6m)
(3m)
(1.5m)
2
2
5'
10'
15'
20'
(1.5m)
(3m)
(4.6m)
(6.1m)
Fig. 1 Closed office
Fig. 2 Open office

Publicité

Table des Matières
loading

Sommaire des Matières pour LEGRAND Wattstopper CI-24

  • Page 1 Wattstopper ® 360° Passive Infrared Low Voltage Occupancy Sensor IRP 360 ° Détecteur de présence de basse tension Sensor de ocupación PIR de 360° de bajo voltaje No: 24216 – 08/16 rev. 1 Installation Instructions • Instructions d’Installation • Instrucciones de Instalación Catalog Numbers •...
  • Page 2: Sensor Adjustment

    INSTALLATION A 4-S junction box can be used with a 3” mud-ring when local building codes mandate that low voltage connections be contained in a junction box. Otherwise a 3” mud-ring or the provided ceiling attachment ring can be used. IMPORTANT: If the lens will be masked, the junction box or mud ring may need to be positioned so that the mask is oriented properly when the sensor is installed (see Masking).
  • Page 3: Ordering Information

    TROUBLESHOOTING LED does not flash with motion 1. Determine if the lens is masked in the direction being tested (see Masking). 2. Check that the Sensitivity setting is set to maximum (DIP switch #3 to ON). 3. Check that the Red and Black wire connections from sensor are secure. 4.
  • Page 4: Instructions De Câblage

    PLACEMENT Les distances de portée réelles peuvent être légèrement inférieures à la distance de détection maximum (voir Diagrammes de couverture), en fonction des obstacles, tels que des meubles ou cloisons, et cela doit être pris en compte lors de la détermination du nombre de détecteurs ainsi que de leur position.
  • Page 5: Réglages De L'interrupteur Dip

    RÉGLAGES DE L’INTERRUPTEUR DIP N° d'interrupteur DIP 1 2 3 4 Temporisations 30 secondes 10 minutes 20 minutes 30 minutes Sensibilité Maximum Minimum ON DIP Service Service Contrôle par Normal interrupteur DIP = MARCHE = ARRÊT pour la temporisation, = Préréglages en usine la sensibilité, et l'entretien RÉGLAGE DU DÉTECTEUR Le détecteur est préréglé...
  • Page 6: Informations Concernant Les Commandes

    INFORMATIONS CONCERNANT LES COMMANDES Numéro de catalogue Description CI-24 Détecteur de présence 24 VCA ou 24 VCC avec une lentille à portée étendue (standard) CI-24-1 Détecteur de présence 24 VCA ou 24 VCC avec une lentille à portée réduite/haute densité INSTRUCCIONES EN ESPAÑOL Les détecteurs sont blancs.
  • Page 7: Instrucciones De Cableado

    INSTALACIÓN Una caja de conexiones 4-S se puede usar con un anillo empotrable de 3 in cuando los códigos de construcción locales obligan que las conexiones de Cielo raso bajo voltaje estén contenidas en una caja de conexiones. De lo contrario, se Orificio de 2-3/4”...
  • Page 8: Configuración Del Interruptor Dip

    No. 24216 – 08/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

Ce manuel est également adapté pour:

Wattstopper ci-24-1

Table des Matières