Technical Data; Control Switch Ghg 29; Am72 Measuring Instrument - Eaton Crouse-Hinds Série Mode D'emploi

Commutateur de commande pour atmosphères explosives et commutateur de commande avec instrument de mesure
Masquer les pouces Voir aussi pour Crouse-Hinds Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
X = fixing dimensions
Control swich GHG 292

Control switch GHG 293,

with meas. instrument with c.t. connection
Control switch GHG 293,
with mes. instrument with direct connection
8
Control switch, GHG 292 and control switch with
measuring instrument, GHG 293
1

Technical data

1.1
Control switch GHG 29:
Marking acc. to 2014/34/EU:
EC type examination certificate:
complete
switch base Ex 29
switch base Ex 28
Rated voltage Ex 29:
Rated voltage Ex 28:
Rated current Ex 29:
* with rated current >12 A terminal cross section > 2.5 mm².
Rated current Ex 28:
Permissible ambient temperature:
Other temperatures possible with special
versions.
Perm.ambient temperature in original packing:
Perm. short-circuit back-up fuse:
Switching capacity Ex 29:
Switching capacity Ex 28:
Design with gold-tipped contacts:
Rated voltage
Rated current
Degree of protection to EN/IEC 60529:
Insulation class acc. to EN/IEC 61140:
Cable entries:
GHG 292
GHG 293 with c.t. measuring instrument
GHG 293 with directly indicated meas.
instrument
Cabel entry:
Test torque for screw in thread cable entry (Nm) 3.0
Seal 1+2+3
1 2
3
(Ø mm/Nm)
Seal 1+2
1 2
3
(Ø mm/Nm)
Seal 1
1 2
3
(Ø mm/Nm)
Terminals (standard version):
Test torques:
Cover screws
Terminals
Weight:
standard version GHG 292
standard version GHG 293 (c.t.)
standard version GHG 293 (direct)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry.
1.2

AM72 measuring instrument:

EC type examination certificate:
Movement:
Measuring accuracy:
Overload range:
Measuring range:
Li:
Ci:
Ui:
Ii:
Terminals:
AM 72 weight:
Max. safe voltage U
:
m
II 2 G Ex d e ia II C T5/T6 T5/T6
II 2 D Ex tD A21 IP66 T80° C
PTB 99 ATEX 1163
BVS 14 ATEX E 119U
BVS 14 ATEX E 076U
up to 500 V, 50/60 Hz
bis 690 V, 50/60 Hz
up to 16 A*
up to 20 A
-20° C up to +40° C (standard version)
-20° C to +40° C
20 A/gL at 500 V
AC 15
230 V / 6 A
DC 13
24 V / 2 A
AC 15
230 V / 8 A
DC 13
24 V / 6 A
24 V
max. 400 mA
IP 66 (standard version)
I - with metal flange
II - plastic terminal boxes fulfil this requirement
(standard version)
1 x M25
1 x M32
2 x M32 and 1 x M25
M25
min.
8.0 / 1.5
max. (1)
10.0 / 2.0
min.
10.0 / 2.3
max. (1)
13.0 / 2.6
min.
13.5 / 1.3
max. (1)
17 .5 / 2.3
2 x 0.5 - 2.5 mm² or 1 x 1.0 - 6.0 mm²
2.5 Nm
2.5 Nm
1 level
approx.
1.10 kg
approx.
2.00 kg
approx.
2.15 kg
BVS 14 ATEX E 125U
Moving iron Ex e IIC Gb Moving coil Ex ib IIC Gb
Class 2.5
10-fold at 25 sec.
25-fold at 4 sec.
50-fold at 1 sec.
telltale 1:1.5
n / 1 A
0 - 25 A direct
-
-
-
-
2 x 1.5 - 4 mm²
approx. 0.40 kg
690 V
eff
Safe galvanic isolation from all other circuits and
earth
E
400 V / 4.0 A
230 V / 0.3 A
500 V / 6.0 A
230 V / 0.4 A
M32
5.0
--
--
14.0 / 3.0
17 .0 / 4.0
17 .5 / 1.5
21.0 / 1.3
2 levels
3 levels
1.25 kg
1.40 kg
2.15 kg
2.30 kg
2.30 kg
2.45 kg
Class 1.5
10-fold at 5 sec.
0 - 20 mA
4 - 20 mA
max. 0.1 mH
max. 0.1 nF
max. 30 V
max. 150 mA