9.3 SPECIFICATIONS DES OPTIONS
Item
Factory Mutual (FM)
CENELEC ATEX
Canadian Standards
Association (CSA)
IECEx Scheme
Certifications combinées
Revêtement autre couleur
autre revêtement Revêtement anti-corrosion
Pièces externes inox 316
Protection antifoudre
Sortie d'état *
11
Dégraissage*
4
4
Dégraissage et séchage*
FM Explosionproof Approval *
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors (NEMA 4X)
FM Intrinsically safe Approval *
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, and Class III, Division 1 Hazardous Locations.
Combined FF1 and FS1 *
1
*
CENELEC ATEX (KEMA) Flameproof Approval *
II 2G Exd IIC T4, T5, T6
CENELEC ATEX (KEMA) Intrinsically safe Approval *
II 1G EEx ia IIC T4
Combined KF21, KS2 and Type n *
Type n: II 3G Ex nL IIC T4
CSA Explosionproof Approval *
Explosionproof for Class I, Groups B, C and D
Dustignitionproof for Class II/III, Groups E, F and G
Enclosure TYPE 4X, Temp.Code:T6...T4
Ex d IIC T6...T4 Enclosure IP66 and IP67
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1, Groups E, F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups E, F and G, Class III, Division 1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annuniciation: at the zero adjustment screw
Combined CF1 and CS1 *
1
IECEx flameproof Approval *
Flameproof for Zone1, Ex d IIC T6...T4
IECEx Intrinsically safe, type n and flameproof Approval *
Intrinsically safe and type n
Ex ia IIC T4, Ex nL IIC T4
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4
Combinaison de /KU21, /FU1 et /CU1 *
Couvercle amplificateur seulement
Deux faces du couvercle amplificateur, Munsell 7.5 R4/14
Plaque signalétique, plaque repère, vis d'ajustement du zéro
Tension d'alimentation transmetteur: 10.5 à 32 V DC ( 10.5 à 30 V DC pour
version à sécurité intrinsèque)
Courant maximum 6000 A (1×40 μs), répété 1000 A (1×40 μs) 100 fois
Normes : IEC 61000-4-4, IEC 61000-4-5
Sortie transistor
Contact :10.5 à 30 VDC, 120 mA DC(max) Niveau bas : 0 à 2 VDC
Dégraissage
Dégraissage avec capsule huile au fluor
Température –20 à 80°C( –4 à 176°F)
Dégraissage et séchage
Dégraissage et séchage avec huile au fluor
Température de fonctionnement –20 à 80°C( –4 à 176°F)
<9. Spécifications générales>
Description
1
1
3
*
3
1
1
*
1
3
*
1
1
*
3
*
3
1
1
*
3
3
1
3
*
IM 01C25B01-01F-E
9-12
Code
FF1
FS1
FU1
KF21
KS2
KU21
CF1
CS1
CU1
SF2
SU2
V1U
P
PR
X2
HC
A
AL
K1
K2
K5
K6

Publicité