Technical Data Table; Single / Single Phase Ups Technical Data Table - Riello UPS Sentinel Dual SDL 8000 Manuel D'installation Et D'utilisation

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2 -
S
/
INGLE
SINGLE PHASE
MODELS
INPUT
Nominal voltage
Accepted range
Voltage range for non-intervention of battery
Nominal frequency
Maximum current (1)
Nominal current (2)
Power factor
Current distortion @ max load
BYPASS
Voltage range accepted for switching
Frequency range accepted for switching
Switching time
BATTERY
Recharge time (8)
OUTPUT
Nominal voltage
Static variation (3)
Dynamic variation (4)
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
Frequency (5)
Current crest factor
Nominal power (VA)
Nominal power (W)
Short circuit current
SUNDRY
Leakage current to earth
AC/AC performance
Ambient temperature (6)
Humidity
Protections
Hold-up time
Noise
Dimensions H x L x D (mm)
Weight in Kg (estimated)
(1) @ nominal load, minimum voltage of 180Vac, battery charging
(2) @ nominal load, nominal voltage of 230Vac, battery charging
(3) Mains/Battery @ load 0% -100%
(4) @ Mains/battery/mains @ resistive load 0%/100%/0%
(5) If the mains frequency is within ±5% (user definable) of the selected value, the UPS is synchronized with the mains. If the
frequency is out of tolerance or in operation from battery, the frequency is the selected value ±0.1%
(6) 20 - 25 °C for extended battery life
(7) Recalibration may be necessary after a long period of operation, in order to maintain the output voltage within the indicated
range.
(8) Time needed to reach 90% of charge (after a full discharge at load ≥80%)
UPS

TECHNICAL DATA TABLE

SDL 8000
from 184 to 138 Vac from 100% to 50% of the linear load
excessive battery discharge - overcurrent - short circuit - overvoltage -
2 x [455mm (19") x 175mm (4U) x 660mm (26")]
approx 29 + 65 Kg
83
T
ECHNICAL DATA TABLE
220/230/240 Vac
0 - 280 Vac
Maximum voltage 276Vac
Minimum voltage:
Return of operation from mains at 190Vac
50 - 60 Hz ±5Hz
44A
34A
0.98
6%
180 – 264 Vac
Frequency selected ±5%
0.1ms
6-8 h
220/230/240 Vac selectable ±1.5%
1.5% (7)
5% in 20ms
Sinusoidal
3%
5%
50 or 60 Hz selectable
3 : 1
8000
7200
1.5 x In for t= 0.5sec
10mA
92%
0 – 40 °C
< 90% non condensing
undervoltage - thermal
30msec
< 45 dB(A) at 1mt.
SDL 10000
54A
43A
10000
9000
approx 30 + 65 Kg