FUNCTION
Alarm threshold
Selects the overload
for maximum
load
Display
Selects the level of
brightness
brightness of the LCD
Selects the mode of
operation of the sound
Sound alarm
Selects the operating
Auxiliary socket
mode of the auxiliary
(power share)
Selects the permitted
range for the input
Input frequency
tolerance
switchover to bypass
synchronization
Selects the permitted
Bypass voltage
voltage range for
thresholds
switchover to bypass
Bypass voltage
Selects the permitted
thresholds for
voltage range for ECO
ECO
mode operation
Selects the sensitivity
Sensitivity of
of intervention during
intervention for
operation in ECO
ECO mode
Power supply of the
Load power
load on bypass with
supply in stand-
UPS switched of
by
(stand-by status)
Selects the mode for
Bypass operation
use of the bypass line
60
DESCRIPTION
PREDEFINED
Disabled
user limit
Maximum
Reduced
alarm
Always
connected
socket

ADVANCED FUNCTIONS

frequency for
± 5%
and for output
Low:
High: 264V
Low:
High: 253V
Normal
mode
Disabled
(load NOT
powered)
Normal
POSSIBLE CONFIGURATIONS
Disabled
0 ÷ 103 in steps of 1%
Minimum ÷ Maximum in 20 steps
Normal
Reduced: does not sound for
momentary intervention of the bypass
Always connected
Cut-out after n seconds of operation
from battery
Cut-out after n seconds from the end of
discharge prealarm signal
... (see configuration software manual)
± 0.25%
± 0.5%
± 0.75%
± 1 ÷ ±10 in steps of 1%
180V
Low :
180 ÷ 200 in steps of 1V
High:
250 ÷ 264 in steps of 1V
200V
Low: 180 ÷ 220 in steps of 1V
High:
240 ÷ 264 in steps of 1V
Low
Normal
High
Disabled (not powered)
Enabled (powered)
Normal
Disabled with input/output
synchronization
Disabled without input/output
synchronization
MODE