UPS C
ONFIGURATION
The following table illustrates all the possible configurations that users have at their disposal to best adapt the
UPS to their needs.
LEGEND:
=
=
FUNCTION
Selects the nominal
Output frequency
output frequency
Selects the nominal
Output voltage
Selects one of the 4
different modes of
Operating mode
automatic switching
Switch-on delay
on again after the
Automatic UPS
switch-off when in
Switch-off due to
battery-powered
minimum load
operation, if the load
Maximum battery
Back-up
limitation
Estimated remaining
End of discharge
back-up time for the
early warning
end of discharge early
Time interval for the
Battery test
automatic battery test
Indicates that the configuration can be modified, both via the configuration
software supplied and also by means of action on the display panel.
Indicates that the configuration can be modified only through the configuration
software supplied.
DESCRIPTION
PREDEFINED
Auto
230V
output voltage
ON LINE
operation
Delay time for
5 sec.
mains returns
Disabled
is less than 5%
Disabled
operation time
3 min.
warning
40 hours
POSSIBLE CONFIGURATIONS
50 Hz
60 Hz
Auto: automatic self-teaching of the
input frequency
220V
230V
240V
220 ÷ 240 in steps of 1V
(only through the software)
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
Disabled
1 ÷ 255 in steps of 1 sec.
Enabled
Disabled
Disabled (full battery discharge)
1 ÷ 65000 in steps of 1 sec.
1 ÷ 255 in steps of 1 min.
Disabled
1 ÷ 1000 in steps of 1 hour
U
SE
MODE
59