General Technical Specifications
Enclosure
Certification
Detection Ranges and Alarm Levels
Gas
Resolution
Detected
Carbon
CO *
monoxide
Hydrogen
H
S
2
sulfide
Nitrogen
NO
2
dioxide
O
Oxygen
2
H
Hydrogen
0.5% LEL
2
CH
Methane
0.5% LEL
4
C
H
Propane
0.5% LEL
3
8
Sensor exposure to gas concentration that may result in permanent damage to the sensor
+
*
Tested by Intertek to UL 2075 for Sensitivity, Selectivity, and Electrical Supervision at 23 ±3
°C (73 ±5°F) and 50 ±20 %RH
Sensor Over Range
Sensor over range occurs whenever the detected gas
concentration level is higher than the full scale value of the sensor.
When an over range condition occurs, the LCD displays
"OVRRANGE" and the buzzer sounds for 50 milliseconds, once
every 10 minutes.
The LED blinks once per second normally but twice per second
during an over range condition.
When the gas concentration falls back within the full scale range
of the cell, the the buzzer is silenced and the LCD displays the
current concentration.
E
Point Gas Monitor Technical Manual
3
Polycarbonate
Safety Requirements For Electrical Equipment For Measurement, Control,
And Laboratory Use - Part 1: General Requirements [UL 61010-1:2012
Ed.3+R:29Apr2016]
Safety Requirements For Electrical Equipment For Measurement, Control, And
Laboratory Use – Part 1: General Requirements (R2017) [CSA C22.2#61010-1-
12:2012 Ed.3+U1;U2]
Range
1 ppm
0-250 ppm
0.1 ppm
0-50 ppm
0.1 ppm
0-10 ppm
0.1%vol
0-25%vol
0-100%LEL
0-100%LEL
0-100%LEL
Alarm A
Alarm B
25 ±2 ppm 100 ±5 ppm 200 ±10 ppm
10 ppm
15 ppm
0.7 ppm
2 ppm
19.5%vol.
22%vol.
25%LEL
50%LEL
25%LEL
50%LEL
25%LEL
50%LEL
Specifications
Maximum
Alarm C
Overload
500 ppm
20 ppm
150 ppm
9 ppm
150 ppm
22.5%vol
100%vol
90%LEL
100% LEL
90%LEL
100% LEL
90%LEL
100% LEL
33