General Technical Specifications
Enclosure
Certification
Detection Ranges and Alarm Levels
Gas
Resolution
Detected
Carbon
CO *
monoxide
Hydrogen
H
S
2
sulfide
Nitrogen
NO
2
dioxide
O
Oxygen
2
H
Hydrogen
0.5% LEL
2
CH
Methane
0.5% LEL
4
C
H
Propane
0.5% LEL
3
8
Sensor exposure to gas concentration that may result in permanent damage to the sensor
+
*
Tested by Intertek to UL 2075 for Sensitivity, Selectivity, and Electrical Supervision at 23 ±3
°C (73 ±5°F) and 50 ±20 %RH
Sensor Over Range
•
Sensor over range occurs whenever the detected gas
concentration level is higher than the full scale value of the sensor.
•
When an over range condition occurs, the LCD displays
"OVRRANGE" and the buzzer sounds for 50 milliseconds, once
every 10 minutes.
•
The LED blinks once per second normally but twice per second
during an over range condition.
•
When the gas concentration falls back within the full scale range
of the cell, the the buzzer is silenced and the LCD displays the
current concentration.
E
Point Gas Monitor Technical Manual
3
Polycarbonate
Safety Requirements For Electrical Equipment For Measurement, Control,
And Laboratory Use - Part 1: General Requirements [UL 61010-1:2012
Ed.3+R:29Apr2016]
Safety Requirements For Electrical Equipment For Measurement, Control, And
Laboratory Use – Part 1: General Requirements (R2017) [CSA C22.2#61010-1-
12:2012 Ed.3+U1;U2]
Range
1 ppm
0-250 ppm
0.1 ppm
0-50 ppm
0.1 ppm
0-10 ppm
0.1%vol
0-25%vol
0-100%LEL
0-100%LEL
0-100%LEL
Alarm A
Alarm B
25 ±2 ppm 100 ±5 ppm 200 ±10 ppm
10 ppm
15 ppm
0.7 ppm
2 ppm
19.5%vol.
22%vol.
25%LEL
50%LEL
25%LEL
50%LEL
25%LEL
50%LEL
Specifications
Maximum
Alarm C
Overload
500 ppm
20 ppm
150 ppm
9 ppm
150 ppm
22.5%vol
100%vol
90%LEL
100% LEL
90%LEL
100% LEL
90%LEL
100% LEL
33