6. Setting addresses and operating units

The address switch of each BC controller is set to "000" when shipped from the
factory.
Set the address switch to 1 + the address of the outdoor unit.
s The BC controller address should generally be set to 1 + the address of
the outdoor unit. However, if this would result in it having the same ad-
dress as another outdoor unit, set the address between 51 and 100, mak-
ing sure that it is different from the address of other controllers.
Please refer to the outdoor unit installation manual.

7. Test run

Before commencing a test run please check the fol-
lowing:
s After installing, piping and wiring the indoor units and BC controllers,
check to see again that there is no refrigerant leakage and no slack on
power and control cables.
s Use a 500 V megger to check that there is an insulation resistance of
more than 1.0 M
between the power terminal block and the ground. If it
is less than 1.0 M , do not operate the unit.
10
s When connecting multiple indoor units to one branch port
Indoor units connected to one branch port can only be operated in the same
mode.
When connecting multiple remote controllers, group setting is required.
Caution:
Never measure the insulation resistance of the terminal block for any control
cables.