7. Electrical work

7.3. Function settings

7.3.1. For wired remote controller (Fig. 7-5)
⁄ Mode number
1
⁄ Setting number
2
⁄ Refrigerant address
3
⁄ Unit number
4
Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function setting mode.
Switch OFF the remote controller.
Press the A and B buttons simultaneously and hold them for at least 2 seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (3) to 00.
3 Press D and [--] will start to flash in the unit number (4) display.
4 Use the C button to set the unit number (4) to 00.
5 Press the E MODE button to designate the refrigerant address/unit number. [--] will flash in the mode number (1) display momentarily.
6 Press the F buttons to set the mode number (1) to 04.
7 Press the G button and the current set setting number (2) will flash.
Use the F button to switch the setting number to the power supply voltage to be used.
Power supply voltage
240 V
: setting number = 1
220 V, 230 V : setting number = 2
8 Press the MODE button E and the setting number (1) and (2) will change to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two seconds. The function selection screen will disappear momentarily and the air conditioner
OFF display will appear.
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Auto mode
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
No. of air outlets
Installed options (high-performance filter)
Up/down vane setting
Energy saving air flow
(Heating mode)
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled
Settings
100Hr
2500Hr
No filter sign indicator
Standard (PLH/PLA-P·AA(H)/PLA-RP·AA)/Silent (PLH/PLA-P·KA(H),
PCH/PCA)
High ceiling 1 (PLH/PLA-P·AA(H)/PLA-RP·AA)/Standard (PLH/PLA-
P·KA(H), PCH/PCA)
High ceiling 2 (PLH/PLA-P·AA(H)/PLA-RP·AA)/High ceiling (PLH/
PLA-P·KA(H), PCH/PCA)
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup 1)
Equipped with vanes (vanes angle setup 2)
Disabled
Enabled
Mode no.
Setting no. Initial setting
1
01
2
1
02
2
3
1
03
2
3
1
04
2
1
05
2
Mode no.
Setting no. Initial setting
1
07
2
3
1
08
2
3
1
09
2
3
1
10
2
1
11
2
3
1
12
2
Setting
Setting
9