SERVICING
Maintenance and inspection of this product must be carried
out in accordance with EN 12056-4 and EN 60074-19.
To ensure continued reliability of service, we recommend that
you take out a service contract.
WARNING!
Before carrying out any works: disconnect the pump and the
controls from the mains and take steps to ensure that it cannot
be emergized again.
WARNING!
Check the mains cable for signs of mechanical and chemical
damage. Damaged or kinked cables must be replaced by the
manufacturer.
NOTICE! When using a chain to lift the pump, please observe
the relevant national regulations regarding accident preventi-
on. Lifting gear must be checked regularly by an expert in ac-
cordance with the legal regulations.
NOTICE! Motors in the Ex-range conform to the "flameproof
enclosures" ignition protection category. Maintenance works
that affect the explosion protection may only be carried out by
authorised specialists or by the manufacturer. When carrying
out repairs, all areas next to flameproof gaps must be checked
for damages and, if necessary, replaced by genuine parts.
Oil check
The oil reservoir is sealed on the outside with a sealing screw
"Öl" (oil). In order to check the mechanical seal, the oil, includ-
ing any residue, must be drained from the oil reservoir and col-
lected in a clean measuring container.
• If the oil is contaminated with water (milky), an oil change
must be carried out. Check again after a further 300 operat-
ing hours, but at the very latest after 6 months!
• However, if the oil is contaminated with both water and pol-
lutants, then not only the oil must be replaced, but the me-
chanical seal as well.
For monitoring the oil reservoir, it is also possible to retrofit
the electrode of our "DKG" or DKG-Ex" seal leak control device
in place of the "DKG" sealing screw.
Changing the oil
To ensure operational liability, the first oil change should be
carried out after 300 operating hours, with further oil changes
carried out after every 1000 operating hours.
If the number of operating hours is very low, an oil change
should still be carried out at least once a year.
If wastewater with strongly abrasive constituents is being
pumped, the oil changes should be carried out at correspond-
ingly shorter intervals.
Use HLP hydraulic mineral oil, viscosity class 22 to 46, e.g. Mo-
bil DTE 22, DTE 24, DTE 25, to replace the oil in the oil reservoir.
The volume of oil required is 520 cm³ for MultiCut 25/2 to 36/2
and 750 cm³ for MultiCut 45/2.-
NOTICE! The oil reservoir may only be filled with the specified
quantity of oil. Overfilling will result in the pump being rendered
inoperable.
10
Checking the pump unit
The housing screws for the pump, and the connecting and fix-
ing screws of the installation must be checked to ensure they
are fixed securely. They should be tightened if necessary.
If the pump performance decreases, or if increasingly loud
noises can be heard during operation, or if the cutting perfor-
mance decreases (the pump tends to become blocked), the
impeller and cutting system must be checked for wear by an
expert and replaced if necessary.
Replace the impeller
CAUTION!
Worn impellers can have sharp edges.
1. Block the cutting rotor with a piece of wood and unscrew
the central hexagon socket screw
2. Remove the compression piece and screw the extraction tool
(code no. JP50325) into the thread of the cutting rotor. Tight-
ening the inner screw pulls the cutting rotor off the pump
shaft.
3. Unscrew the four hexagon socket screws on the top of the
spiral housing, and take off the spiral housing.
4. Fit the new impeller with the feather key onto the shaft,
using the same number of adjusting washers as before.