7a. Use a 7/16 inch deep socket set to install orifice marked #47
onto rear orifice holder. Use needle-nose pliers to screw rear
target onto rear orifice holder (30 only). See Figure 7.
7b. Use a 7/16 inch deep socket set to install orifice marked
2.40 mm onto rear orifice holder. Use needle-nose pliers to
screw rear target onto rear orifice holder (35 only).
See Figure 7.
8a. Use a 7/16 inch deep socket set to install orifice marked #52
onto front orifice holder. Use needle-nose pliers to screw
front target onto orifice holder (30 only). See Figure 7.
8b. Use a 7/16 inch deep socket set to install orifice marked #50
onto front orifice holder. Use needle-nose pliers to screw
front target onto orifice holder (35 only). See Figure 7.
9.
Loosen rear air shutter screw and rotate handle to the left
until 1/8 inch opening is achieved. Tighten screw. See Figures
8 and 9.
10. Loosen the front air shutter screw and lower the air shutter
until it stops. Then tighten the screw. See Figure 10.
Figure 8 - Rear Burner Air Shutter
41346-1-0220
ORIFICE
TARGET
Figure 7
Empire Comfort Systems Inc. • Belleville, IL
Figure 9 - Rear Burner Air Shutter
Figure 10 - Front Burner Air Shutter
11. Use a 7/16 inch open wrench to loosen pilot body by slightly
turning counter clockwise. Slide orifice bracket to other side
and tighten pilot body clockwise. See Figure 11.
12. Replace items removed in steps 2-5 in reverse order.
13. Adjust damper and air shutter for perfect burn.
14. Gas conversion is completed.
Check the main burner flame and pilot burner flame must be
checked for proper flame characteristics, as outlined in the
Installation Instructions.
NAT
VERIFY INPUT RATE OF CONVERTED FIREPLACE
Check the input of the fireplace:
1. Turn off all other gas appliances. Clock the gas meter and
determine the number of seconds required to consume one
cubic foot of gas.
2. 3600 ÷ time (in seconds) = cu. ft. per hour.
3. Then cu. ft. per hour x heating value of gas = input rate
(Btu/hr). On installation without gas meters, check manifold
for proper pressure.
If fireplace is not installed or project registration card has not
been returned to Empire Comfort Systems, check off type of gas
converted to on the card. Also indicate conversion by adding
"Conv." behind type of gas.
CLOSED
OPEN
NAT
Figure 11
Page 3