Guidelines For Locating Smoke Detectors And Co Detectors; Smoke Detectors - DSC HS2TCHP Guide De L'utilisateur

Masquer les pouces Voir aussi pour HS2TCHP:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Guidelines for Locating Smoke Detectors and CO Detectors

Guidelines for Locating Smoke Detectors and CO
Detectors
The following information is for general guidance only and it is recommended that local fire codes and reg-
ulations be consulted when locating and installing smoke and CO alarms.

Smoke Detectors

Research has shown that all hostile fires in homes generate smoke to a greater or lesser extent. Experiments
with typical fires in homes indicate that detectable quantities of smoke precede detectable levels of heat in
most cases. For these reasons, smoke alarms should be installed outside of each sleeping area and on each
storey of the home. The following information is for general guidance only and it is recommended that local
fire codes and regulations be consulted when locating and installing smoke alarms. It is recommended that
additional smoke alarms beyond those required for minimum protection be installed. Additional areas that
should be protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace
and utility rooms; and any hallways not protected by the required units. On smooth ceilings, detectors may
be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling height, air
movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72,
CAN/ULC-S553-02 or other appropriate national standards for installation recommendations.
Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these
l
locations may prevent the unit from detecting smoke.
Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement
l
around the detector may prevent smoke from entering the unit.
Do not locate detectors in areas of high humidity.
l
Do not locate detectors in areas where the temperature rises above 38oC (100oF) or falls below
l
5oC (41oF).
Smoke detectors should always be installed in USA in accordance with Chapter 29 of NFPA 72, the
National Fire Alarm Code: 29.5.1.1.
Where required by other governing laws, codes, or standards for a specific type of occupancy, approved
single- and multiple-station smoke alarms shall be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a sleep-
ing room, with the distance measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including basements and
excluding crawl spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
- 28 -

Publicité

Table des Matières
loading

Table des Matières