INSTALLATION
5. There is excessive condensation on windows in the
winter.
6. A ventilation system is installed in the house.
Slide the hose clamp over the aluminium flex pipe.
Then slide the flex pipe over the air intake tube of the
stove. Next tighten the hose clamp over the end of the
aluminium flex hose.
FOR USE IN MOBILE HOME/TRANSPORTABLE
BUILDINGS
• WARNING! DO NOT INSTALL IN SLEEPING
ROOM.
• CAUTION!
THE
OF
THE
MOBILE
BUILDING FLOOR, WALL, AND CEILING/ROOF
MUST BE MAINTAINED.
• INSTALL IN ACCORDANCE WITH 24 CFR, PART
3280 (HUD).
• USE A FACTORY BUILT CHIMNEY THAT
COMPLIES
WITH
THEREFORE IT MUST BE A TYPE HT (2100°F).
• USE A SPARK ARRESTER.
• THE STOVE MUST BE ATTACHED TO THE
STRUCTURE
OF
TRANSPORTABLE BUILDING.
SECURE APPLIANCE TO THE FLOOR
Use the designated holes to secure the unit to the floor.
STRUCTURAL
INTEGRITY
HOME/TRANSPORTABLE
UL
103
STANDARDS;
THE
MOBILE
HOME/
In addition to the previously detailed installation
requirements, the heater must be electrically grounded
to the steel chassis of the Mobile Home/Transportable
Buildings with 8 GA copper wire using a serrated or star
washer to penetrate paint or protective coating to ensure
grounding.
CHIMNEY CONNECTOR (STOVE PIPE)
Install
crimped
end
towards
stove.
Flow
Direction
of Flue
Gases
The chimney connector and chimney must have the same
diameter as the stove outlet (6"). If this is not the case,
we recommend you contact your dealer to ensure there
will be no problem with the draft. The stovepipe must be
made of aluminized or cold roll steel and have a minimum
thickness of 0.021" or 0.53 mm. It is strictly forbidden
to use galvanized steel. The smoke pipe should be
assembled to promote the male section (crimped end) of
the pipe to be faced down. Attach each section to another
with three metal screws spaced an equal distance apart.
The pipe must be short and straight. All sections installed
horizontally must slope at least 1/4 inch per foot, with
the upper end of the section toward the chimney. Any
installation with a horizontal run of chimney pipe must
conform to NFPA 211. To ensure a good draft, the total
length of the coupling pipe should never exceed 8' to 10'
(2.4m to 3.04m). Except for cases of vertical installation,
in a cathedral-roof style where the smoke exhaust
system can be much longer and connected without
problem to the chimney at the ceiling of the room. There
should never be more than two 90 degrees elbows in the
smoke exhaust system. The installation of a "barometric
draft stabilizer" (fireplace register) on a smoke exhaust
system is prohibited. Furthermore, the installation of
a draft damper is not recommended. With a controlled
combustion wood stove, the draft is regulated upon
intake of the combustion air in the stove and not at the
exhaust.
7
© 2023 United States Stove Company
1/4" slope per foot
Male Part Downwards
3 screws