Output
Table 3.
kW (208 V)
DROP 4
DROP 6
DROP 7
DROP 9
*
In case there are any uninsulated brick, tile, or glass walls in the sauna room, an additional 4,8 ft³
must be added to the sauna room volume for each 1 ft² of such wall; or 1,5 m³ for each 1 m²
ATTENTION!
You shall not use a non-heat-resistant cable with PVC isolation as the
power cable. When using the junction box in the sauna room, it should be
waterproof and located at a maximum height of 19.7 in (50 cm) from the floor.
• Open the cover of the heater's electrical box.
• Take the cable into the electrical box through the rubber bushing.
• Attach the power cable on the terminal block according to the circuit diagram.
ATTENTION!
reflector.
• Close the cover.
• Fix the cable on the bushing with a cable strap.
• Install the heater on the wall frame and ensure that it stays firmly in place.
DROP 4
DROP 6
Room*
88-194 ft
3.4
2.5-5.5 m
141-282 ft
4.5
4-8 m
176-317 ft
5.6
5-9 m
211-388 ft
6.75
6-11 m
The cable should first pass through the opening in the heater
L1
L2
240V 2~
208V 2~
Amps
A
3
16.35
3
3
21.63
3
3
26.92
3
3
32.44
3
DROP 7
DROP 9
Circuit Breaker
A
20
30
30
40
L1
L2
240V 2~
208V 2~
Min.Wire Size
AWG
10
10
8
8
7