Configuration
Condensed programming menu
This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it.
Condensed programming menu
OUT OF
PROGRAMMING
Temperature
indication
Parameters
SP Temperature setting (Set Point)
CE SELFDRIVE Mode 0=Deactivated 1= Activated
C1 Sensor 1 differential (Hysteresis)
d0 Defrost frequency (time between 2 starts)
d1
Maximum defrost duration (0=defrost deactivated)
d4
Final defrost temperature (by sensor) (If I00 ¹ 1)
SH
Superheating set point
F3 Status of the fans during the defrost 0=Stopped; 1=Running
A1
Alarm for maximum in sensor 1 (it must be higher than the SP)
A2 Alarm for minimum in sensor 1 (it must be lower than the SP)
d30 Defrost strategy in SELFDRIVE mode
* According to the set-up wizard.