STEP 4
CHECKING WIRING AND PLUMBING: Check all wiring and
plumbing inside and outside of the wall to be sure none will be
broken where the hole is to be cut.
STEP 5
HOLE CONSTRUCTION: Depending upon size of unit to be
installed, lay out the hole dimensions per the chart below. Cut
and frame in hole to fi nished dimensions. Use 2" x 4" material for
framing and follow the suggested typical installations in Figure
C, D, or E.
NOTE: IF THE WALL CONSTRUCTION IS TYPICAL FRAME
OR 2 x 4 STUDDING WITH BRICK OR STONE VENEERS,
LOCATE THE HOLE NEXT TO ONE OF THE STUDS. FOR
MASONRY, CONCRETE OR CINDER BLOCK WALLS,
LOCATE HOLE FOR CONVENIENCE.
FINISHED
SMALL
DIMENSION
CHASSIS
A
16
3
⁄
"
16
3
B
26
⁄
"
16
NOTE: THESE DIMENSIONS ARE FOR FINISHED HOLE SIZE.
Figure C
FRAME WALL CONSTRUCTION
CAULK ALL SIDES
CABINET
ELECTRICAL
RECEPTACLE
(SEE FIG. E FOR
LO CA TION NOTE)
16
MEDIUM
LARGE
CHASSIS
CHASSIS
18
3
⁄
"
20
3
⁄
"
16
8
3
1
26
⁄
"
28
⁄
"
16
4
SHIM THE VOID
SPACE AT THE
TOP AND SIDES
WITH WOOD AS
REQUIRED
920-198-00
Figure D
BRICK VENEER CONSTRUCTION
CAULK ALL SIDES
CABINET
Figure E
SOLID MASONRY CONSTRUCTION
CAULK
ALL SIDES
CABINET
MOR TAR
NOTE: ELECTRICAL RECEPTACLE LOCATION FROM
POINT "X" MUST BE WITHIN A MAXIMUM RADIUS OF
69" FOR 115V UNITS AND 45" FOR 230V UNITS.
SHIM VOID SPACES AT TOP AND
SIDES WITH WOOD AS REQUIRED
ELECTRICAL RECEPTACLE
(SEE FIGURE E FOR
LOCATION NOTE)
ELECTRICAL
RE CEP TA CLE
POINT "X"