Operation
(continued)
Shutdown Messages
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: During all these
conditions, the "Input," "Output" and "Bypass" LEDs will be illuminated.
201207113 933070.indb 27
SHUTDOWN
LCD DISPLAY
CONDITIONS
MESSAGES
Extended
SHUT DOWN
Overload
OVERLOAD XXX%
Output Short
SHUT DOWN
Circuit
O/P SHORT CIRCUIT
Bypass SCR
SHUT DOWN
Short Circuit
BYPASS SCR FAIL
Input SCR
SHUT DOWN
Rectifier Fails
RECTIFIER SCR FAIL
Inverter Output
SHUT DOWN
Short Circuit
INVERTER FAIL
SHUT DOWN
Output SCR Failure
OUTPUT SCR FAIL
SHUT DOWN
Input Fuse Open
I/P FUSE BROKEN
SHUT DOWN
Output Fuse Open
O/P FUSE BROKEN
Parallel Wire
SHUT DOWN
Connection Failure
PARALLEL FAULT
SHUT DOWN
Internal
+ DC BUS HIGH
Faults
SHUT DOWN
+ DC BUS LOW
SHUT DOWN
- DC BUS HIGH
SHUT DOWN
- DC BUS LOW
SHUT DOWN
BUS OVP FAIL
SHUT DOWN
OVERTEMPERATURE
27
9/17/2012 1:20:09 PM