Operation
Normal Operation
During normal operation, the first line of your LCD Display shows which operating mode your UPS is in: Online Mode, Economy Mode,
Frequency Conversion Mode, Battery Mode, Bypass Mode or Parallel Mode (12kVA model only).
Online Mode: The UPS provides AC power while utility power is available and switches to On Battery Mode instantly (zero transfer time) if
AC power is interrupted.
Economy Mode: The UPS provides AC power at high efficiency while utility power is within +/- 10% rated AC input voltage and switches to
On Battery Mode (8ms transfer time) if AC power is interrupted.
Frequency Conversion Mode: Used to convert your UPS's input frequency to a different output frequency (i.e. Input 60 Hz to Output 50
Hz. Note: Output will be turned off in Frequency Conversion Mode if the unit is put into Bypass).
Battery Mode: The UPS provides AC power from battery backup so long as battery power lasts. It switches back to Online or Economy
Mode if utility power is available and shuts down if it runs out of battery power.
Bypass Mode: The UPS provides AC power while utility power is available. The UPS shuts down if AC power is interrupted.
Parallel Mode (SU12KRT4UHW model only): The UPS can provide redundancy up to 6kVA or power up to 12kVA. Refer to the manual
provided with the Parallel PDU Kit for more information.
The second line of the LCD Display shows basic power conditions. In each operating mode you can push the SCROLL buttons to browse
through these basic power conditions in the sequences shown below:
Display Information
Online Mode:
ONLINE MODE
00.00KW / 000%
M
STANDALONE
00.00KVA / 000%
M
INPUT VOLTAGE
000V / 00.0Hz
M
BYPASS VOLTAGE
000V / 00.0Hz
M
OUTPUT VOLTAGE
000V / 00.0Hz
M
BATTERY CAPACITY
000V / 000%
M
REMAINING TIME
0000 MINUTES
M
ON-LINE 5/6KVA
V00 CV01
201207113 933070.indb 17
(continued)
Display Information
Economy Mode:
ECONOMY MODE
00.00KW / 000%
M
STANDALONE
00.00KVA / 000%
M
INPUT VOLTAGE
000V / 00.0Hz
M
BYPASS VOLTAGE
000V / 00.0Hz
M
OUTPUT VOLTAGE
000V / 00.0Hz
M
BATTERY CAPACITY
000V / 000%
M
REMAINING TIME
0000 MINUTES
M
ON-LINE 5/6KVA
V00 CV01
Display Information
Display Information
Frequency
Battery Mode:
Conversion Mode:
FREQ CONV MODE
00.00KW / 000%
M
STANDALONE
00.00KVA / 000%
M
INPUT VOLTAGE
000V / 00.0Hz
M
BYPASS VOLTAGE
000V / 00.0Hz
M
OUTPUT VOLTAGE
000V / 00.0Hz
M
BATTERY CAPACITY
000V / 000%
M
REMAINING TIME
0000 MINUTES
M
ON-LINE 5/6KVA
V00 CV01
17
Display Information
Bypass Mode:
BATTERY MODE
BYPASS MODE
00.00KW / 000%
00.00KW / 000%
M
STANDALONE
STANDALONE
00.00KVA / 000%
00.00KVA / 000%
M
INPUT VOLTAGE
INPUT VOLTAGE
000V / 00.0Hz
000V / 00.0Hz
M
BYPASS VOLTAGE
BYPASS VOLTAGE
000V / 00.0Hz
000V / 00.0Hz
M
OUTPUT VOLTAGE
OUTPUT VOLTAGE
000V / 00.0Hz
000V / 00.0Hz
M
BATTERY CAPACITY
BATTERY CAPACITY
000V / 000%
000V / 000%
M
REMAINING TIME
REMAINING TIME
0000 MINUTES
0000 MINUTES
M
ON-LINE 5/6KVA
ON-LINE 5/6KVA
V00 CV01
M
M
M
M
M
M
M
V00 CV01
9/17/2012 1:20:08 PM