IMPORTANT INFORMATION
Health & Safety
1 This appliance should ONLY be fitted and serviced by a competent & qualified HVAC/R installer
in accordance with these instructions and all relevant local and national electrical codes and
regulations.
2 This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved.
3 Children shall not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
4 If the supply cord is damaged the pump must be switched off to avoid a hazard. Any
replacement of the power cord is intended to be made by the manufacturer, its service agent or
similar qualified person.
5 When servicing or replacing the head tube, switch off the isolator to isolate the pump from the
electrical supply or disconnect from the electrical supply following the National wiring rules. Peri
Pro float is provided with high level safety wiring for disabling the AC system in the event of a
high level or failure to prevent damage occurring.
INSTALLATION – INTRODUCTION
The pump is designed to be fitted remotely from the AC unit, for example in the ceiling void, to lift
condensate water where a gravity drain is too obtrusive or not possible. A run-on timer is fitted
with the Air sensor variant so that excess condensate does not overflow the drip tray when the unit
switches off, either on thermostat or at the end of use.
This pump is designed to sit level on its base and must at all times have adequate space around it for
good ventilation. Ensure that there are no kinks or trapped parts in the piping, which must have an
inside diameter of 6mm.
In the event of a product fault, please return to the manufacturer. The pump casing is not intended to
be opened and contains no field serviceable parts.
Peri Pro Air
The red (hot) sensor is to be placed on the air inlet of the air conditioner, the blue (cold) sensor is to
be placed on the air outlet of the air conditioner. When a differential temperature of greater than 5ºC
occurs between the two sensors, the pump will operate.
How to set the speed on Peri Pro Air
While powering up press and hold the test button on the rear of the pump for 10s. The front LED will
begin to flash. Button can then be released. Pressing the button again will then cycle through the
below options:
LED
Single slowflash
Double medium flash
Fast triple flash
Turn off the power to the pump and the desired speed will be set.
+
Peri Pro
The reservoir is placed next to the AC unit within the drip tray drainage line and will operate the
pump when condensate enters the reservoir, lifting the float and activating the operating sensors.
+
S
Peri Float is provided when a high level safety wiring for disabling the AC system in the event
of a high level event to prevent damage occurring. See the typical Wiring diagram for connection
instructions.
INSTALLATION – HIGH LEVEL WIRING
POWER 110V–230V
(L1) LIVE: Brown • (L2) NEUTRAL: Blue
118mm
76mm
WATER OUTPUT
5LPH
10LPH (Default)
15LPH
HIGH LEVEL CUT OUT / VOLT FREE
Black (Common)
Black (N.C.)
INSTALLATION – TYPICAL WIRING
PERI PRO AIR (FP3390)
PUMP
MOTOR
PCB
Peristaltic Pump
+
(FP3391)
PERI PRO
PUMP
MOTOR
PCB
Peristaltic Pump
Pump sensor cable
Ceiling
Suction hose to pump
Unit drip tray
Evaporator/
drip tray outlet
indoor unit
Note: Typical dimensions shown apply to Peri Pro
Both Peri fault mode: If the pump is running at full speed and the LED is flashing, Please check
your connections to the sensor float/ air sensor leads.
+
Peri Pro Air & Pro
1. Inspect the pump head regularly and change the pump head tube every 12 months or more often
if required. If any problems with the pump occur check the tube first!
2. Loosen the visor fixing screw, unclip and remove the visor. Unscrew both inlet and outlet hoses
from the head tube assembly. To remove the pump head tube, make sure the roller assembly is
vertical. Slide the inlet and outlet connectors from their housings and carefully remove from the
roller assembly. Fit the replacement hose and refit the roller assembly visor by reversing the above
procedure.
3. Press the test button to operate the roller assembly to check the pump is correctly operating.
4. Replacement pump head tubes and other accessories can be obtained from the wholesalers.
Please quote the serial number (to be found on the pump) when ordering spare parts.
+
Peri Pro
5. The float filter and chamber should be cleaned annually or more often if required.
2
red air sensor in return air
Blue air sensor
(Cold air outlet)
> 5ºC differential pump runs
Test
Live (Brown)
Neutral (Blue)
Common (Black)
Normally closed (Black)
3m
90m
Discharge hose
to drain
For every 1m of suction the
pump power
head is reduced by 1m.
cable
Max 3m suction.
12m combined
reservoir
lift and suction
+
& Peri Pro Air models. Example shown is Peri Pro
FAULT FINDING
MAINTENANCE
Live (Brown)
Neutral (Blue)
12m
head
from
0m
max
3m
suction
lift
+
.
EN