IMPROPER INSTALLATION
The use of other components other than stated
herein could cause bodily harm, heater damage,
and void your warranty. The manufacturer will not
be held responsible for damage caused by the
malfunction of a stove due to improper venting or
installation.
FLOOR PROTECTION
This heater must have a non-combustible floor
protector (UL1618 ember protection) installed
beneath it if the floor is of combustible material.
US - Floor protector should be UL listed or equal too,
needs to extend 6" to the front, 6" to each side, 1" to
the rear of the unit. Under and 2" beyond each side
of the cleanout tee if an interior vertical installation.
Canada - Floor protector should comply with CAN/
ULC standards. Needs to extend 18" to the front, 8"
beyond each side of the unit.
A
Back to Stove
B
Side to Stove
C
Front to Stove
D
Back to Flue
© 2022 United States Stove Company
U.S.A 1"
26mm
CAN
8" 204 mm
U.S.A 6"
153 mm
CAN
8" 204 mm
U.S.A 6"
153 mm
CAN
8" 204 mm
2"
51 mm
INSTALLATION
CLEARANCES
Your pellet stove has been tested and listed
for installation in residential, mobile home in
accordance with the clearances given below. For
safety reasons, please adhere to the installation
clearances and restrictions. Any reduction in
clearance to combustibles may only be done by
means approved by a regulatory authority.
E
Side Wall to Stove
F
Side Wall to PL Vent Pipe
G
Back Wall to Stove
H
Back Wall to PL Vent Pipe
J
Ceiling to Floor
K
Ceiling to Stove
L
Side Wall to Stove
M
Side Wall to PL Vent Pipe
N
Back Wall to PL Vent Pipe
6
10"
245 mm
11-1/2"
292 mm
11-7/8"
302 mm
3"
76 mm
84"
2134 mm
53-7/8' 1434 mm
7-1/2"
191 mm
11-1/4"
286 mm
7-1/2"
191 mm