Calibrate the temperature on your appliance so that it matches the room temperature.
Parameters
Accessibility
Language
Date / Time
Open windows
Calibra�on
Calibra�on
Step 2/4:
Place the reference
thermometer in the centre
of the room, ideally 1.2 m
above the floor
Next
Calibra�on
There may be a difference
between the room temperature
and the value set on the radiator
Current compensa�on: 0°C
Procedure
Change
Our devices are compatible with various load shedding systems. However, you must not
use mains shut-off load shedding, since these systems are incompatible with our devices.
Sudden, inadvertent and repeated power shut-offs can cause premature wear and damage
to the electronics boards, which would not be covered by the manufacturer's warranty.
During load shedding periods, the screen shows "Prioritized load shedding" if an Off/Load
shedding command is sent, and "Priority command" if a frost protection command is sent.
The appliance will then return to its initial operation.
CALIBRATION
Calibra�on
There may be a difference
between the room temperature
and the value set on the radiator
Current compensa�on: 0°C
Procedure
Change
Calibra�on
Step 3/4:
Allow the room to stabilise
(at least 6 hours at the same
temperature)
Next
Calibra�on
Once the room has stabilised,
the reference thermometer
indicates
21.0 °C
(Compensa�on: -2°C)
Confirm
LOAD SHEDDING
73
Calibra�on
Step 1/4:
Choose a cold day,
when the outside temperature
is at least 10°C lower
than the room
Next
Calibra�on
Step 4/4:
Read the temperature
on the thermometer, then
compensate for the difference
on the radiator
I understand
EN