5.
Taking into operation
Prior to operation, check the light fitting for its
proper functioning and installation in compli-
ance with these operating instructions and
other applicable regulations!
– Only carry out insulation measurements
between PE and the external conductor
L1(L,L2,L3) as well as between PE and N!
– measuring voltage: max. 1 kV AC/DC
– measuring current: max. 10 mA
– The light use only in closed area.
Explosion protected light fittings zone 2 and zone 22
Series: KXB-......
6.
Maintenance
Observe the national regulations
applicable to the maintenance, servicing
and test of electrical apparatus as well as
the general rules of engineering
(e.g. IEC/EN 60079-17)!
Servicing
When servicing, in particular those components
that affect the type of protection, will have to
be checked, e. g.:
– Housing and protective bowl for any cracks or
damages.
– Gaskets for their perfect condition.
– Terminals and blanking plugs for their firm fit.
– Because of the risk of an electrostatic charge,
the light fitting shall only be cleaned with a
damp cloth or sponge!
Only use customary household washing-up
liquid diluted in water as specified! The water
temperature may be max. 50 ºC. After that,
rinse with clear water to prevent the risk of
tension cracks in the protective bowl!
– Lamp replacement: Keep replacement
intervals as specified by the lamp manufacturer!
7.
Repair
Prior to replacing or removing any
components, observe the following:
Cut the apparatus off the voltage before
opening it or carrying out repairs! Cut off
as well the battery circuit!
Only use certified genuine ZUMTOBEL spare
parts (see appropriate spare parts list)!
8
Disposal/Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal will have to be observed.
In case of disposal you can obtain additional
information from your ZUMTOBEL branch.
Subject to modifications or supplement of the
product range.