Télécharger Imprimer la page

Victron energy BLUE POWER QUA248020010 Manuel page 25

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 57
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the
leader L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
Float
ds8-ds7
voltage
voltage
14.1
13.8
off
off
28.2
27.6
56.4
55.2
14.4
13.8
off
on
28.8
27.6
57.6
55.2
14.7
13.8
on
off
29.4
27.6
58.8
55.2
15.0
13.8
on
on
30.0
27.6
60.0
55.2
ds6: absorption time 8 or 4 hours (not relevant for L2, L3)
ds5: adaptive charging characteristic (not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (not relevant for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to
'off' and do not reflect the actual settings in the microprocessor).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of
the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other settings' can always be recovered.
Storage
Suitable for
voltage
13.2
Gel Victron Long Life (OPzV)
26.4
Gel Exide A600 (OPzV)
52.8
Gel MK battery
Gel Victron Deep Discharge
13.2
Gel Exide A200
26.4
AGM Victron Deep Discharge
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.2
Tubular plate (OPzS) batteries in
26.4
semi-float mode
52.8
AGM spiral cell
13.2
Tubular plate (OPzS) batteries in
26.4
cyclic mode
52.8
DS-8
off
DS-8
DS-7
off
DS-7
DS-6
on
DS-6
DS-5
on
DS-5
DS-4
off
DS-4
DS-3
off
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
Step 2
Step 2
Example 2:
Example 3:
8, 7 OPzV 14,1V
8, 7 AGM 14,7V
6 Absorption time: 8 h
6 Absorption time: 8 h
5 Adaptive charging: on
5 Adaptive charging: on
4 Dyn. current limit: off
4 Dyn. current limit: on
3 UPS function: off
3 UPS function: off
2 Voltage: 230V
2 Voltage: 240V
1 Frequency: 50Hz
1 Frequency: 50Hz
on = 8 hours
off = 4 hours
on = active
off = inactive (fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 230V / 120V
off = 240V / 115V
on = 50Hz
off = 60Hz
on
DS-8
on
off
DS-7
on
on
DS-6
off
on
DS-5
off
on
DS-4
off
off
DS-3
on
off
DS-2
off
on
DS-1
off
Step 2
Example 4:
8, 7 Tubular-plate 15V
6 Absorption time: 4 h
5 Fixed absorption time
4 Dyn. current limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
21

Publicité

loading