2.0
Password
2001
Pressing at the same time the
Load
password 2001
and confirms
→
↑
moves the cursor
↵
increases the loaded value
confirms
01/16 10783331 WEB E cod.MF72...
I
P-E
+
keys
, you display page:
P-E
2.1
External CT ratio
Ct =
external primary/secondary CT ratio
External CT ratio (Ct): 1...9999
→
↑
moves the cursor
↵
increases the loaded value
confirms
External VT ratio
Vt =
external primary/secondary VT ratio
External VT ratio (Vt): 1,00...10,00
For voltage direct connection (with external voltage transformer) load
Vt=1,00
By modifying the
CT
and/or
reset
→
↑
moves the cursor
↵
increases the loaded value
confirms
Nemo 72 Le
(ex.: CT 800/5A Ct = 160)
(max. primary current 50000/5A - 10000/1A)
(ex.: TV 600/100V Vt = 6)
(max. primary voltage TV 1200V)
VT
ratios, the KWH meters are automatically
13