PROGRAMMING
T-SERIES
BUFFER VPD SETTING
The buffer figure will create a trigger-off point
below your set trigger point to prevent your
device from shutting off too quickly. Press
the up or down button to cycle through buffer
range from 0.1 kPa and 1.0 kPa.
BUFF.
In high VPD triggers, your device will turn on,
only turning off when the VPD falls below your
buffer setting.
In low VPD triggers, your device will turn on,
only turning off when the VPD rises above your
set buffer setting.
2.51
kPa
EXAMPLE
In this example, your High VPD Trigger is set at
2.51 kPa and your VPD Buffer is set at 0.2 kPa.
2.31
kPa
Your device will trigger on when it meets or
rises above 2.51 kPa, and only trigger off when
it falls below 2.31 kPa%. The 2.51 kPa figure
is obtained by taking your High VPD Trigger
of 2.51% and subtracting your VPD Buffer of
0.2 kPa.