5.5.2 Step 2: Other settings
The remaining settings are not relevant (na) for slaves.
Some of the remaining settings are not relevant for follow ers (L2, L3). These settings are imposed on the w hole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
Absorption
ds8-ds7
voltage
14.1
of f
of f
28.2
56.4
14.4
of f
on
28.8
57.6
14.7
on
of f
29.4
58.8
15.0
on
on
30.0
60.0
ds6: absorption time 8 or 4 hours (na for L2, L3)
ds5: adaptive charging characteristic (na for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (na for L2, L3)
(the w ide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exem plary settings for stand-alone m ode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP sw itches of a new product are set to 'off' and do
not reflect the actual settings in the microprocessor.).
DS-8 Ch. v oltage
of f
DS-7 Ch. v oltage
on
DS-6 Absorpt. time
on
DS-5 Adaptiv e ch.
on
DS-4 Dy n. Curr. limit
of f
DS-3 UPS f unction:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptiv e charging: on
4 Dy namic current limit: of f
3 UPS f unction: on
2 Voltage: 230V
1 Frequency : 50Hz
To store the settings after the required values have been set: press the 'Dow n' button for 2 seconds (lower button to the right of the DIP
sw itches). The temperature and low-battery LED's w ill flash to indicate acceptance of the settings.
You can then leave the DIP sw itches in the selected positions, so that the 'other settings' can alw ays be recovered.
20
Float
Storage
oltage
voltage
13.8
13.2
Gel Victron Long Lif e (OPzV)
27.6
26.4
Gel Exide A600 (OPzV)
55.2
52.8
Gel MK battery
Gel Victron Deep Discharge
13.8
13.2
Gel Exide A200
27.6
26.4
AGM Victron Deep Discharge
55.2
52.8
Stationary tubular plate (OPzS)
AGM Victron Deep Discharge
13.8
13.2
Tubular plate traction batteries in
27.6
26.4
semi-f loat mode
55.2
52.8
AGM spiral cell
13.8
13.2
Tubular plate traction batteries in
27.6
26.4
cy clic mode
55.2
52.8
DS-8
of f
DS-8
DS-7
of f
DS-7
DS-6
on
DS-6
DS-5
on
DS-5
DS-4
of f
DS-4
DS-3
of f
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
Step 2
Step 2
Example 2:
Example 3:
8, 7 OPzV 14,1V
8, 7 AGM 14,7V
6 Abs. time: 8 h
6 Abs. time: 8 h
5 Adaptiv e ch.: on
5 Adaptiv e ch: on
4 Dy n. Curr. limit: off
4 Dy n. Curr. limit: on
3 UPS f unction: of f
3 UPS f unction: of f
2 Voltage: 230V
2 Voltage: 240V
1 Frequency : 50Hz
1 Frequency : 50Hz
Suitable for
on = 8 hours
off = 4 hours
on = active
off = inactive
on = active
off = inactive
on = active
off = inactive
on = 230V
off = 240V
on = 50Hz
off = 60Hz
on
DS-8
on
of f
DS-7
on
on
DS-6
of f
on
DS-5
of f
on
DS-4
of f
of f
DS-3
on
of f
DS-2
of f
on
DS-1
of f
Step 2
Example 4:
8, 7 Tub.-plate 15V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dy n. Curr. limit: off
3 UPS f unction: on
2 Voltage: 240V
1 Frequency : 60Hz
(inactiv e = f ixed absorption time)