Three phase operation (appendix D)
Step 1: Setting ds2 and ds1 for 3-phase operation
Leader (L1)
DS-8 AC input
Set
DS-7 AC input
Set
DS-6 AC input
Set
DS-5 AES
na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Leader
on
DS-1 Leader
of f
As the table above show s, the AC-in current limits for each phase should be set separately (ds8 thru ds6). Different current limits per
phase can be selected.
If a panel is connected, the AC input current limit w ill equal the value set on the panel for all phases.
AES can be used on stand alone units only.
The maximum charge current is the same for all devices, and should be set on the leader only (ds4 and ds3).
Exam ple: 9kVA 3-phase system without Multi Control Panel
- AC input current limit on the leader and the follow ers: 12A
- If the charge current on the leader is set to 100% (70A for a Multi 48/5000/70) and the system consists of three devices, then the
effective system charging current is equal to 3 x 70 = 210A.
The settings according to this example (9kVA 3-phase system without Multi Control Panel) are as follow s:
Leader (L1)
DS-8 AC input
12A
DS-7 AC input
12A
on
DS-6 AC input
12A
DS-5 AES
na
DS-4 Ch. current 3x70A
on
DS-3 Ch. current 3x70A
on
DS-2 Leader
on
DS-1 Leader
To store the settings after the required values have been set: press the 'Up' button of the leader for 2 seconds (upper button to the right
of the DIP sw itches, see appendix A, position K). The overload and low-battery LED's w ill flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP sw itches to apply the remaining settings (step 2).
Follow er (L2)
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 na
DS-4 na
DS-3 na
DS-2 Follower 1
of f
DS-1 Follower 1
of f
Follower (L2)
of f
DS-8 AC in 12A
of f
DS-7 AC in 12A
on
of f
DS-6 AC in 12A
of f
DS-5 na
DS-4 na
DS-3 na
DS-2 Follower 1
of f
of f
DS-1 Follower 1
of f
Follow er (L3)
DS-8 Set
DS-7 Set
DS-6 Set
DS-5 na
DS-4 na
DS-3 na
DS-2 Follower 2
of f
DS-1 Follower 2
on
Follower (L3)
DS-8 AC in 12A
of f
DS-7 AC in 12A
on
DS-6 AC in 12A
of f
DS-5 na
DS-4 na
DS-3 na
DS-2 Follower 2
of f
DS-1 Follower 2
on
19