TECHNICAL DATA
Supply voltage
Max load
IP rating
Power consumption
Temperature range
Humidity sensor/combined sensor
Display type
Connection terminals
Installation configuration
Dimensions
(LxWxH)
Warranty
Standards
Only qualified personnel (electrician or similar qua-
lification) may install the device. The relevant en-
gineering practices and the enclosed safety instruc-
tions must be observed!
The Ice and Snow Detector 1873 is a single-chan-
nel basic device that can be used for all applica-
tions in the field of ice and snow detection. With
the 1875 extension unit and the Modbus or LAN
gate-ways, the 1873 can be expanded into mul-
ti-functional systems with up to 8 sensors/heating
channels and connection to the internet or a build-
ing management system.
A comprehensive alarm management checks
both the internal device functions and those of the
con-nected sensors. Furthermore, the function of
the heating relay and a downstream contactor can
be monitored.
195-253V / 50Hz
3600W (16A)
IP20
3 W
-30 °C .. +80 °C
Tekmar 3354 & 3356
Backlit graphical touch screen
Screw terminals w. spring load 2,5 mm²
DIN-rail TH-35
90 x 53 x 60 mm
5 years
CE • RoHS • UKCA
5
WARRANTY
3