Application
Adjustment of the application. This setting adapts the functions of the 1873 and its menu to the configura-
tion in which it is used.
Factory setting: Single Unit
Sensor type
Adjustment of the type of combi sensor connected to the respective ice detection channel.
The sensor type must be set for each ice detection channel during commissioning. If the "to be defined"
setting is maintained, an error message with an alarm will be displayed.
Factory setting: to be defined
Server communication active
In case of a System or Multi Channel configuration without Internet Gateway, the communication to the
TAV Server can be deactivated here. In this case, no error message appears in the idle display.
Factory setting: Yes
Remaining inhibition time moisture
Display of the remaining inhibition time of the sensor in minutes. During a moisture measurement the sen-
sor is heated up and has to cool down again for up to 30 minutes before taking the next measurement.
The re-maining inhibition time shows when the next measurement can start at the earliest.
Zone number
Display of the number of the zone in which the channel is registered.
Operating time total
Display of the total operating hours a heating circuit has accumulated since the device has last been reset
to its factory settings.
Energy consumption total
Display of the total heating energy used since the device has last been reset to its factory settings. This
value is the product of the heating performance and the value of the resettable operating time counter (in
kWh).
State, OAT measurement & Weather series
23