SETTINGS
Upper temperature limit
Adjustment of the upper temperature limit (activation temperature) valid for the ice detector or the se-
lected ice detection channel. Below this temperature the moisture measurement will be activated.
Factory setting: +3 °C
Moisture treshold
Adjustment of the moisture threshold for the ice detector or the selected ice detection channel. A setting
of 0.5 is very sensitive, i. e. the heating may react if the sensor is completely dry. A setting of 9.5 is very
insensitive, i. e. the heating only reacts if a large amount of moisture has accumulated.
Factory setting: 5.0
Minimum heating time
Adjustment of the minimum heating time for the ice detector or the selected ice detection channel. The
minimum heating time is started once moisture is detected in standby mode.
Factory setting: 90 min
Start minimum heating time
One-time activation of the heating for the duration of the minimum heating time.
Week programs 1-4
Adjustment of a week/time program for a zone. The week program applies to ice detection channels
assigned to the respective zone. In the "System" application one week program is available. In the "Multi
Channel" application one week program per zone can be used. 16 switching points can be defined for
each week program.
With a week program, the control mode of the zone is time-controlled. Each day of the week can be
defined individually or together with other weekdays in a time grid of 15 minutes.
Example:
1.
Select Menu
2.
Press >>.
3.
Use the plus or minus button (+ or -) to select the entry that is to be changed, for example Entry 1.
18
Operation
Week program.