Adapting the upstream fuse /transformer options
 Only cooling units with the rated operating voltage 400V / 460V can be optionally connected to a different mains
voltage.
 Reconnection takes place via the supply of the primary side of the transformer.
 The upstream fuse must match the changed mains voltage; see Adapting the upstream fuse.
1
Figure 16 - Transformer options
Voltage Range (V)
50 Hz
360 V - 418 V
360 V - 440 V
378 V - 440 V
-
414 V - 484 V
-
414 V - 506 V
-
432 V - 506 V
3.5.6
Components for internal protection
Cooling units have several safety components.
2
1
Figure 17 – Components for internal protection
Operating Manual DTS and DTI 6801 Multi-Controller (MC) 086100008c © Pfannenberg GmbH
 The specifications for the factory settings of the transformer are 
provided on the yellow connection diagram (1) on the rear side of the
unit.
 UL-conformity with the following fuses:
Category "ClassCC", slow-burning.
1
Transformer - Optionen
60 Hz
T1/ 1 [0] – T 1/ 3 [380]
-
380 V
T1/ 1 [0] – T 1/ 4 [400]
-
400 V
T1/ 1 [0] – T 1/ 5 [420]
-
420 V
T1/ 1 [0] – T 1/ 6 [440]
440 V
T1/ 1 [0] – T 1/ 7 [460]
460 V
T1/ 1 [0] – T 1/ 8 [480]
480 V
 Functional equipotential-bonding M8 thread (1), for a
signal reception with low interference between the unit and
the switch cabinet.
Protective equipotential-bonding (2) for metal
components and touch voltage.
Pre-fuse (Min. 480 V)
Max. 4 A
Max. 4 A
Max. 4 A
Max. 4 A
Max. 2,5 A
Max. 2,5 A