The instructions set out here only concern connections to be carried out by the installer.
The electrical panel is pre-wired in the factory. Wiring should under no circumstances be modified at the risk of
damage or injury.
It is very important to use cables with a cross section that is adequate for the current that they will carry.
Check that connections are correctly tightened.
An inadequately sized cable or loose connection could heat up and start a fire.
According to the French standard C15-100, a 30 mA residual current device must be installed at the head of the
line .
5.
Key switch
The key switch must be installed in a place from which the entire pool is visible. This will allow the person
operating the key switch to unroll the cover over the pool to ensure that there is no-one in the pool for the entire
duration of the operation (NF P90-308 requirement).
Lay a duct between the key switch and the electrical panel to run the cables.
6.
Electrical wiring
Check that the electrical panel terminals are connected to their corresponding terminals in the deck box.
Check that the stripped sections of the wires are tightened correctly in their terminal contacts.
The electrical connections to be made are as follows:
220 – 240 V
1ph/ 50 Hz
Cable 3 x 2.5
2
PROTECTION & SÉCURITÉ
CAUTION
Electrical panel terminals
For slaving
"cover open"
3g4
2
up to 20 m
3g6
2
up to 30 m
HO7RNF or
HO6RNF
Deck box terminal block
3x1
2
shielded
18
Key switch
box
2021/09 - Indice de révision : B - Code : 34690