FS-3 / FS-3N
MONITOR
SOP
Store Output Parallel (latching function outputs 1/2)
If the parameter is active, the outputs do not switch back automatically in case of a fault.
They must be reset internally or externally.
The function is simultaneously activated for both outputs.
The reset function is also effective for both outputs.
• Values: 0 = inactive / 1 = active front reset / 2 = front and external reset
• Default value: 0
DIM
Dimension (display format)
Indication in Hz or RPM (revolutions per minute)
• Values: 0 = RPM / 1 = Hz
• Default value: 0
VER
Software Version
Possibility to look at the installed software version
(5-digit number with the abbreviation VCO)
Application parameters
Parameter Description, values, default value
SPx
Switch Point (switch point, number of differential pulses)
Number of differential pulses at which the respective output switches,
(e.g. SPx = 5, the relay de-energises when the 5th differential pulse is reached).
• Werte: 1...999
• Voreinstellung: 1
HYx
Hysteresis (number of hysteresis pulses)
The hysteresis value determines the distance of the switch-off point to the switch
point SPx. It must be set to a value < SPx .
Switch-off point = SPx - HYx.
• Values: 1...99
• Default value: 1
DTx
Delay Time (delay time)
Enables a delayed switching of the outputs 1/2.
In case of a value greater than 0.0 s the outputs only switch if the state of being above
or below the switch point is longer than the time set.
If e.g. for DTx = 5 s the allowed number of differential pulses is exceeded but is already
below this value after 3 s, the output does not switch.
• Values: 0.0...1000.0 s (only effective if SOP inactive, 0)
• Default value: 0.0 (no delay time)
FTx
Fleeting Time (fleeting function)
If an event occurs, the output changes its state during the set time and then switches
back to the initial state.
• Values: 0.0...1000.0 s
• Default value: 0.0 (fleeting time not active)