Coelbo EPR Manuel D'utilisation page 6

Publicité

Les langues disponibles

Les langues disponibles

BASIC MENU
+
(diagram C)
- Press simultaneously
- By mean of
or
- Press
for validation.
- This is the parameters sequence:
TYPE
SYSTEM REACTION
bar psi We can select the pressure units
displayed beetween bar and psi.
ADVANCED MENU
- Press simultaneously
- By mean of
or
- Press
for validation.
- The parameters sequence is:
SCREEN
SYSTEM REACTION
Activation of the automatic restore
Ar0
Ar1
system ART (Ar1) o disable (Ar0).
In case of enabled ART, it can be
n01
n48
set the number of restore at-
tempts, between 1 and 48.
It can be set the span of the at-
t10
t40
tempt between 10 and 40 seconds.
Stand-by disabled (Sb0) or
Sb0
Sb1
enabled (Sb1)
With P_ON is activated a mini-
mum operating pressure. Under
P0.0 P_ON
this pressure is activated an alarm
(A11).
Time, in seconds, under minimal
t05
t99
pressure necessary to activate A11.
Anti-flooding configuration.
If activated, it stops the pump af-
ter programmed time (in minutes)
H00
H99
of continuous operation.
Disabled (H00), 1 minute (H01) ...
99 minutes (H99).
rs0
rs1
Restore factory settings (rs1)
REGISTER OPERATION DATA AND ALARMS
- Press simultaneously
- Press
to advance in the REGISTER.
- The DATA sequence is:
MESSAGE
DESCRIPTION
rEc
HF
Controller operating hours
HP
Pump operating hours
Operating cycles
CF
Number of start-stop cycles.
Number of connections to the
Cr
power supply.
A01
Number of A01 alarms.
+
during 5 seconds.
the values can be changed.
+
+
+
+
during 5 seconds.
the values can be changed.
+
+
during 5 seconds.
0-65535
0-65535
0-999999
0-65535
0-999
A02
A05
A11
APM
FACTORY
SETTING
rPM
bar
rSt
PRESSURE SENSOR CALIBRATION
In case of wrong lecture of the pressure sensor it can be
adjusted again.
For the pressure sensor calibration is necessary to have a
FAC-
pressure gauge in the installation. Proceed following next
TORY
steps:
SET-
TING
ZERO REGULATION
1.
Open the taps living the hydraulic net without pressure.
Ar1
2.
Press simultaneously the buttons
display show 0.0 flashing.
3.
Press
48
FULL SCALE
1.
Set the outlet pressure equal to the maximum pressure
15"
of the pump. In case of using a pump with higher pres-
sure than 6 bar, set the outlet pressure to 6 bar. (Go to
0
the point 4 of the STARTUP to remember how to set the
outlet pressure)
2.
Start the device and wait until it stops the pump.
0.0
3.
Press simultaneously the buttons
play flashes with a figure.
4. Adjust the pressure with the arrows push-buttons to get
20
the pressure desired.
5.
Press
Examples:
H00
MAXIMUM PUMP
PRESSURE
rs0
4 bar
8 bar
+
+
Remark: pressure sensor decalibration should not be
a normal event. If it is frequently repeated contact the
technical service.
SCOPE
6
Number of A02 alarms.
Number of A05 alarms.
Number of A11 alarms.
Number of times the device has
registered higher pressure than
11bar / 160PSI
Maximum pressure registered
by the device.
ENTER -> EXIT.
+
-> All the alarms are
restored
except the operation data.
to validate.
to validate.
OUTLET
PRESSURE
4 bar
6 bar
0-999
0-999
0-999
0-999
and
until the
and
till the dis-
ADJUSTED FULL
SCALE
4 bar
6 bar

Publicité

loading

Ce manuel est également adapté pour:

Dpr