value = 1 = 0x1
snc4000 > envMonRangeShow
Air Inlet Temp (C):
Nominal: 5 to 45
Warning: 4 <= N < 5 or 45 < N <= 50
Alarm:
N < 4 or N > 50
IO Processor Temp (C):
Nominal: 5 to 80
Warning: 4 <= N < 5 or 80 < N <= 108
Alarm:
N < 4 or N > 108
Input Power: +5 Volts (V):
Nominal: 4.94 to 5.35
Warning: 4.83 <= N < 4.94 or 5.35 < N <= 5.46
Alarm:
N < 4.83 or N > 5.46
Input Power: +12 Volts (V):
Nominal: 11.62 to 12.62
Warning: 11.50 <= N < 11.62 or 12.62 < N <= 12.87
Alarm:
N < 11.50 or N > 12.87
Local Power: +2.5 Volts (V):
Nominal: 2.40 to 2.58
Warning: 2.36 <= N < 2.40 or 2.58 < N <= 2.62
Alarm:
N < 2.36 or N > 2.62
Local Power: +3.3 Volts (V):
Nominal: 3.20 to 3.39
Warning: 3.13 <= N < 3.20 or 3.39 < N <= 3.46
Alarm:
N < 3.13 or N > 3.46
Fan (RPM):
Nominal: 2520 to 3780
Warning: 2205 <= N < 2520 or 3780 < N <= 4095
Alarm:
N < 2205 or N > 4095
value = 1 = 0x1
envMonRangeShow
La commande envMonRangeShow spécifie les plages opérationnelles pour les canaux environnementaux
du SNC 4000. Elle affiche les plages de valeurs associées aux états nominaux, d'avertissement et d'alarme
relatifs à la tension, la température et le fonctionnement du ventilateur/de la soufflerie selon les canaux
spécifiés dans la commande envMonShow.
SNC4000 > envMonRangeShow
Air Inlet Temp (C):
Nominal: 5 to 45
Warning: 4 <= N < 5 or 45 < N <= 50
Alarm:
Air Outlet Temp (C):
Nominal: 5 to 50
Warning: 4 <= N < 5 or 50 < N <= 55
Alarm:
IO Processor Temp (C):
Guide de l'utilisateur de SNC 4000
N < 4 or N > 50
N < 4 or N > 55