Basic configuration
b00 Delay of all functions on receiving power supply
b01 Cold room light timing
Password function 0=inactive
b10
1=parameter access lock 2=keypad lock
PAS
Password
b20 MODBUS address
Communication speed: 0=9600 bps 1=19200 bps
b21
2=38400 bps 3=57600 bps
b22 Audible alarm enabled 0=no 1=yes
Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor
b23
S5, 5=superheating, 6=pressure sensor, 7=% EEV, 8=% eFAN, 9=carousel,
10=off
Unt Working units 0=ºC 1=ºF
EP
Output to level 1
Inputs and outputs
St Type of probes connected: 0= NTC, 1= Pt1000
Probes connected: 1=sensor 1 (cold room), 2=sensor 1 (cold room) + sensor
I00
2 (evaporator)
D1/S3 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
I10
6=defrost lockout, 7=low pressure switch, 8=remote activation in Stand-by
mode, 9=product temperature
Digital input polarity D1: 0=activates on closing, 1=activates on opening
I11
contact
D2/S4 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
I20
6=defrost lockout, 7=high pressure switch for hot gas, 8=remote activation of
Stand-by mode, 9=product temperature, 10=defrost 2
Digital input polarity D2: 0=activates on closing, 1=activates on opening
I21
contact
D3/S5 input configuration: 0=deactivated, 1=door contact, 2=external alarm,
3=severe external alarm, 4=change SP, 5=remote defrost,
I30
6=defrost lockout, 7=remote activation of Stand-by mode, 8=rroduct temper-
ature, 9=superheating temperature (Sh)
Digital input polarity D3: 0=activates on closing, 1=activates on opening
I31
contact
* According to the set-up wizard.
Description
Description
evaporator
nd
31
351652671 Ed. 02
Values Min. Def. Max.
min.
0
0
255
min.
0
0
999
0
0
2
0
0
99
1
1
247
bps
0
0
3
0
1
1
1
*
10
0
0
1
Values Min. Def. Max.
0
0
1
1
2
2
0
*
9
0
0
1
0
*
10
0
0
1
0
9
9
0
0
1