Expansion valve
Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV
u00
2=Stepper-type EEV
SH Superheating set point
Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A,
5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A,
u02
12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C,
19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A
u03
PWM cycle time
u04 Proportional constant value (P)
u05 Integral constant value (I)
u06 Derivative constant value (D)
u07 Opening value of the electronic expansion valve when cooling is activated
u08 Duration of valve opening on cooling demand
Valve opening value with sensor error S5 or S6: 0=fixed opening according to
u09
u10; 1=average opening over the last 24 hours
u10
Valve opening value with sensor error S5 or S6 (if u09=0)
Manual valve opening value (0=disabled), (cycles acc. to u03)
u11
Requires safety code. See user manual.
u12 Maximum valve opening value
u13
Minimum valve opening value
u14 Valve opening value after defrost (0=disabled), (duration according to u15)
u15 Duration of valve opening after defrosting
u16 Valve opening in case of LOP error (0=valve closed)
EP
Output to level 1
* According to the set-up wizard.
Description
29
351652671 Ed. 02
Values Min. Def. Max.
0
1
2
K
0.1
8
40
0
*
17
s.
2
6
10
1
10 100
0
10 100
0
0
100
%
u13 50 u12
s.
2
5
240
0
0
1
%
u13
0
u12
%
u13
0
u12
%
u13 100 100
%
0
0
u12
0/
%
0
u12
u13
s
0
0
240
0/
%
0
u12
u13