Step 3*:
Define the minimum value of the pressure sensor (I62) (value at 4 mA, 0 V, 0.5 V or 1 V according to I61).
Step 4*:
Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V, 4.5 V or 10 V according to I61).
*Steps only visible if u02=7
Step 5:
Select the temperature set point.
Step 9:
Set all other parameters to default?
dFP=0
No, the other parameters do not need to be changed
dFP=1
Yes, set all other parameters to their default values
This option only appears if this is not the first time the set-up wizard has been run.
The initial configuration is now complete, and the device will start to regulate the temperature.
The configuration wizard will not reactivate. To reactivate it, activate the stand-by mode (by pressing the
m key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up
permanently) and press the , , SET buttons in this order in sequence, not at the same time.
If the Pump Down function is active, there may be a delay between the initiation of the Stand-by function
and the moment the controller stops.