Télécharger Imprimer la page

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

en
es
fr
351652671 Ed. 02
AKO-16526 V2
Controlador de temperatura y expansión electrónica
para cámara frigorífica
Temperature and electronic expansion controller for
cold room store
Contrôleur de température et détendeur électronique
pour chambre froide
Guía rápida / User manual / Manuel d'utilisateur

Publicité

loading

Sommaire des Matières pour AKO 16526 V2

  • Page 1 351652671 Ed. 02 AKO-16526 V2 Controlador de temperatura y expansión electrónica para cámara frigorífica Temperature and electronic expansion controller for cold room store Contrôleur de température et détendeur électronique pour chambre froide Guía rápida / User manual / Manuel d’utilisateur...
  • Page 2 -Entre –40 ºC y +20 ºC, si se prolonga la sonda NTC hasta 1.000 m con cable de mínimo 0,5 mm , la desviación máxima será de 0,25 ºC (Cable para prolongación de sondas ref. AKO-15586 / AKO-15586H. Conectar la malla a tierra sólo en uno de sus extremos).
  • Page 3 351652671 Ed. 02 Descripción Controlador de temperatura con salida para regulación de valvula de expansión electronica y control de la velocidad de los ventiladores de evaporador. Puede configurarse para que, además de regular el frío de la cámara, pueda controlar el sobrecalentamiento y regular la velocidad de los ventiladores de evaporador mediante un variador o usando ventiladores electrónicos.
  • Page 4 351652671 Ed. 02 Teclado Pulsando durante 3 segundos,activa / desactiva el modo Stand-By. En este modo la regulación se detiene y el display muestra el icono m. En el menú de programación,sale del parámetro sin guardar cambios,retrocede al nivel anterior o sale de programación.
  • Page 5 351652671 Ed. 02 Asistente Al recibir alimentación por primera vez, el equipo entra en modo ASISTENTE. El display muestra el mensaje In{ intermitente con 0. Las teclas  y  varian el valor, la tecla SET acepta el valor y pasa al siguiente paso.
  • Page 6 351652671 Ed. 02  /  / SET Paso 3*: Definir el valor mínimo de la sonda de presión (I62) (Valor a 4 mA, 0 V, 0.5 V ó 1 V según I61). Paso 4*: Definir el valor máximo de la sonda de presión (I63) (Valor a 20 mA, 5 V, 4.5 V ó 10 V según I61). ...
  • Page 7 351652671 Ed. 02 Funcionamiento Mensajes Error de funcionamiento de la recogida de gas (Paro), se ha superado el tiempo configura- do en el parámetro C20. Sólo se muestra en pantalla. Error de funcionamiento de la recogida de gas (Arranque), se ha superado el tiempo con- figurado en el parámetro C19.
  • Page 8 351652671 Ed. 02 Alarma de sobrecalentamiento mínimo, se ha alcanzado el valor definido en A20. Activa el relé de alarma y la alarma acústica. Alerta de sobrecalentamiento alto, se ha alcanzado el valor definido en A23. Sólo se mues- tra en pantalla. Alarma de máxima presión de evaporación, se ha alcanzado el valor definido en A26.
  • Page 9 351652671 Ed. 02 Configuración Menu de programación reducido Permite configurar rápidamente los parámetros más utilizados. Para acceder, pulsar la tecla SET durante 3 segundos. Parámetros Descripción Valores Min. Def. Max. SP Ajuste de temperatura (Set Point) ºC/ºF C1 Diferencial de la sonda 1 (Histéresis) ºC/ºF 2.0 20.0 d0 Frecuencia de desescarche (Tiempo entre 2 inicios)
  • Page 10 351652671 Ed. 02 Menú de programación extendido Mediante el menú de programación extendido, podrá configurar todos los parámetros del equipo para adaptarlo a las necesidades de su instalación. Para acceder, pulsar la tecla SET durante 6 segundos. IMPORTANTE: Si se ha configurado la función del código de acceso como bloqueo del teclado (b10=2), o como bloqueo acceso a parámetros (b10=1) al intentar acceder a cualquiera de las dos funciones, se solicitará...
  • Page 11 351652671 Ed. 02 Parámetros Regulación y control Descripción Valores Min. Def. Max. SP Ajuste de temperatura (Set Point) ºC/ºF -50 0.0 99 C0 Calibración de la sonda 1 (Offset) ºC/ºF -20.0 0.0 20.0 C1 Diferencial de la sonda 1 (Histéresis) ºC/ºF 0.1 2.0 20.0 Bloqueo superior del punto de ajuste...
  • Page 12 351652671 Ed. 02 Desescarche Descripción Valores Min. Def. Max. d0 Frecuencia de desescarche (Tiempo entre 2 inicios) d1 Duración máxima del desescarche (0=desescarche desactivado) min. Tipo de mensaje durante el desescarche: 0=Muestra la temperatura real; 1=Muestra la temperatura al inicio del desescarche; 2=Muestra el mensaje dEF Duración máxima del mensaje min.
  • Page 13 351652671 Ed. 02 Válvula de expansión Descripción Valores Min. Def. Max. Tipo de válvula: 0=Solenoide + VE termostatica 1=VEE tipo PWM 2=VEE tipo stepper Sh Set point de sobrecalentamiento Tipo de gas refrigerante: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A, 5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A...
  • Page 14 351652671 Ed. 02 Alarmas Descripción Valores Min. Def. Max. A0 Configuración de las alarmas de temperatura 0=Relativa al SP 1=Absoluta A1 Alarma de máxima en sonda 1 (Debe ser mayor que el SP) ºC/ºF A2 99.0 99.0 A2 Alarma de mínima en sonda 1 (Debe ser menor que el SP) ºC/ºF -50 -50 A1 Retardo de alarmas de temperatura en la puesta en marcha...
  • Page 15 351652671 Ed. 02 Configuración básica Descripción Valores Min. Def. Max. b00 Retardo de todas las funciones al recibir alimentación eléctrica min. b01 Temporización luz cámara min. Función del código de acceso (Password) 0=Inactivo 1=Bloqueo acceso a parámetros 2=Bloqueo del teclado Código de acceso (Password) b20 Dirección MODBUS Velocidad de comunicación: 0=9600 bps 1=19200 bps...
  • Page 16 351652671 Ed. 02 Entradas y salidas Descripción Valores Min. Def. Max. I60 Unidades de presión: 0= bar, 1= Psi Tipo de sensor de presión (S6): 0= Deshabilitado, 1= 4-20 mA, 2= 0-5 V, 3= 0.5-4.5 V, 4= 0-10 V, 5= 1-5 V I62 Valor mínimo de sonda de presión (4mA, 0V, 0,5V, 1) I63 Valor máximo de sonda de presión (20mA, 5V, 4,5V, 10V) Calibración de la sonda de presión (offset)
  • Page 17 Precisión termométrica ..........................±1 ºC Tolerancia de las sondas (NTC/Pt1000) a 25 ºC ..................±0.4 ºC Entradas S1 a S4 ..................Sonda NTC AKO-14901 o sonda Pt1000 Entrada S5 ................Sonda NTC AKO-14950 / 14950-8 o sonda Pt1000 Temperatura ambiente de trabajo ....................-10 ºC a 50 ºC Temperatura ambiente de almacenaje ....................-30 ºC a 60 ºC...
  • Page 18 Warnings -If the device is used without adhering to the manufacturer's instructions, the device safety require- ments could be compromised. Only sensors supplied by AKO must be used for the unit to operate correctly. -From -40°C to +20°C, if the NTC sensor is extended to 1000m with at least a 0.5mm cable, the maximum deviation will be 0.25°C (cable for sensor extension ref.
  • Page 19 351652671 Ed. 02 Description Temperature controller with output for electronic expansion valve regulation and evaporator fan speed control. In addition to regulating the cooling of the cold room, the controller can be configured to control superheating and regulate the speed of the evaporator fans using an inverter or electronic fans. 1: Display;...
  • Page 20 351652671 Ed. 02 Keypad Press and hold for 3 seconds to activate/deactivate the Stand-By mode. In this mode, regulation is paused and the m icon is displayed. In the programming menu, this key exits the parameter without saving changes and returns to the previous level, or exits programming.
  • Page 21 351652671 Ed. 02 Wizard The first time the unit receives the power supply, it will enter into Wizard mode. The display will show the messageIn{flashing at 0. The buttons  and  change the value, the SET button accepts  /  / SET the value and moves on to the next step.
  • Page 22 351652671 Ed. 02  /  / SET Step 3*: Define the minimum value of the pressure sensor (I62) (value at 4 mA, 0 V, 0.5 V or 1 V according to I61). Step 4*: Define the maximum value of the pressure sensor (I63) (value at 20 mA, 5 V, 4.5 V or 10 V according to I61). *Steps only visible if u02=7 ...
  • Page 23 351652671 Ed. 02 Operation Messages Pump down malfunction error (Stop). The time configured in parameter C20 has been exceeded. Only displayed on screen. Pump down malfunction error (Start). The time configured in parameter C19 has been exceeded. Only displayed on screen. Sensor 1, 2, 3, 4, 5 or 6 is faulty (open circuit, crossed circuit, or value outside sensor limits).
  • Page 24 351652671 Ed. 02 Minimum superheat alarm. The value set in A20 has been reached. Activates the alarm relay and the audible alarm. Minimum superheat alert. The value defined in A23 has been reached. Only displayed on screen. Maximum evaporating pressure alarm. The value defined in A26 has been reached. Acti- vates the alarm relay and the audible alarm.
  • Page 25 351652671 Ed. 02 Configuration Condensed programming menu This allows for the most-used parameters to be quickly configured. Press the SET key for 3 seconds to access it. Condensed programming menu OUT OF PROGRAMMING PROGRAMMING 20 sec. Temperature indication Parameters Values Change 3 sec.
  • Page 26 351652671 Ed. 02 Extended programming menu Use the extended programming menu to configure all of the unit’s parameters in order to adapt it to your installation requirements. Press the SET key for 6 seconds to access it. IMPORTANT: if the password function has been configured as a keypad lock (b10=2), or as an access to parameters block (b10=1), you will be requested to enter the password programmed in PAS when attempting to access either of the two functions.
  • Page 27 351652671 Ed. 02 Parameters Regulation and control Description Values Min. Def. Max. SP Temperature setting (Set Point) ºC/ºF -50 0.0 99 C0 Sensor 1 calibration (Offset) ºC/ºF -20.0 0.0 20.0 C1 Sensor 1 differential (Hysteresis) ºC/ºF 0.1 2.0 20.0 Set point top locking ºC/ºF (it cannot be set above this value) Set point bottom locking...
  • Page 28 351652671 Ed. 02 Defrost Description Values Min. Def. Max. d0 Defrost frequency (time between 2 starts) d1 Maximum defrost duration (0=defrost deactivated) min. Type of message during the defrost: 0=sign of the real temperature; 1=sign of the temperature at the start of the defrost; 2=sample of the dEF message Maximum message duration min.
  • Page 29 351652671 Ed. 02 Expansion valve Description Values Min. Def. Max. Valve type: 0=solenoid + EV thermostat 1= PWM-type EEV 2=Stepper-type EEV SH Superheating set point Refrigerant gas type: 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A, 5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A PWM cycle time...
  • Page 30 351652671 Ed. 02 Alarms Description Values Min. Def. Max. A0 Configuration of the temperature alarms 0=relative to SP 1=absolute A1 Alarm for maximum in sensor 1 (it must be higher than the SP) ºC/ºF A2 99.0 99.0 A2 Alarm for minimum in sensor 1 (it must be lower than the SP) ºC/ºF -50 -50 A1 Delay of temperature alarms in the start-up...
  • Page 31 351652671 Ed. 02 Basic configuration Description Values Min. Def. Max. b00 Delay of all functions on receiving power supply min. b01 Cold room light timing min. Password function 0=inactive 1=parameter access lock 2=keypad lock Password b20 MODBUS address Communication speed: 0=9600 bps 1=19200 bps 2=38400 bps 3=57600 bps b22 Audible alarm enabled 0=no 1=yes Lower display function: 1=sensor S2, 2=sensor S3, 3=sensor S4, 4=sensor...
  • Page 32 351652671 Ed. 02 Inputs and outputs Description Values Min. Def. Max. I60 Pressure units: 0=bar, 1=Psi Pressure sensor type (S6): 0=deactivated, 1=4-20 mA, 2=0-5 V, 3=0.5-4.5 V, 4=0-10 V, 5=1-5 V I62 Minimum pressure sensor value (4 mA, 0 V, 0.5 V, 1 V) I63 Maximum pressure sensor value (20 mA, 5 V, 4.5 V, 10 V) Pressure sensor calibration (S2) AUX 1 relay configuration: 0=deactivated, 1=compressor/crankcase resistance,...
  • Page 33 Resolution, adjustment and differential ......................0.1ºC Thermometric accuracy ..........................±1ºC Tolerance of the (NTC/Pt1000) probes at 25°C ...................±0.4ºC Inputs S1 to S4 ..................NTC probe AKO-14901 or probe Pt1000 Inputs S5 .................. NTC probe AKO-14950 / 14950-8 o probe Pt1000 Working ambient temperature ......................-10ºC to 50ºC Ambient storage temperature ......................-30ºC to 60ºC...
  • Page 34 -Entre –40 °C et +20 °C, si la sonde NTC est prolongée jusqu'à 1 000 m avec un câble d'au moins 0,5 mm l'écart maximum sera de 0,25 °C (câble pour prolongation de sondes, réf. AKO-15586 / AKO-15586H. Raccorder le treillis à la terre uniquement sur une des extrémités).
  • Page 35 351652671 Ed. 02 Description Contrôleur de température avec sortie pour la régulation du détendeur électronique et le contrôle de la vitesse des ventilateurs d’évaporateur. Il peut être configuré afin que, outre réguler le refroidissement de la chambre, il puisse contrôler la surchauffe et régler la vitesse des ventilateurs d’évaporateur à...
  • Page 36 351652671 Ed. 02 Clavier Appuyez pendant 3 secondes pour activer/désactiver le mode Stand-By. Dans ce mode, le réglage s'arrête et l'écran affiche l'icône m. Dans le menu de programmation, sortez du paramètre sans enregistrer les changements, revenez au niveau précédent ou sortez de la programmation. Un appui court affiche la température de la sonde S2 pendant 10 secondes (si elle est activée).
  • Page 37 351652671 Ed. 02 Assistant Lorsqu'il est alimenté pour la première fois, l'appareil entre en mode AS- SISTANT. L'écran affiche le messageIn{clignotant avec 0. Les touches  et  modifient la valeur, la touche SET accepte la  /  / SET valeur et passe à...
  • Page 38 351652671 Ed. 02  /  / SET Étape 3* : Définir la valeur minimale de la sonde de pression (I62) (valeur à 4 mA, 0 V, 0,5 V ou 1 V selon I61). Étape 4* : Définir la valeur maximale de la sonde de pression (I63) (valeur à 20 mA, 5 V, 4,5 V ou 10 V selon I61). *Étapes visibles uniquement si u02=7 ...
  • Page 39 351652671 Ed. 02 Fonctionnement Messages Erreur de fonctionnement du Pump Down (arrêt), le temps configuré dans le paramètre C20 a été dépassé. Le message s'affiche uniquement à l'écran. Erreur de fonctionnement du Pump Down (mise en marche), le temps configuré dans le paramètre C19 a été...
  • Page 40 351652671 Ed. 02 Alarme de surchauffe minimale, la valeur définie en A20 a été atteinte. Active le relais d'alarme et l'alarme sonore. Alerte de surchauffe élevée, la valeur définie en A23 a été atteinte. Le message s'affiche uniquement à l'écran. Alarme de pression d’évaporation maximale, la valeur définie en A26 a été...
  • Page 41 351652671 Ed. 02 Configuration Menu de programmation réduit Permet de configurer rapidement les paramètres les plus utilisés. Pour y accéder, appuyer sur la touche SET pendant 3 secondes. Menu de programmation réduit HORS DE PROGRAMMATION PROGRAMMATION 20 sec. Indication Paramètres Valeurs température 3 sec.
  • Page 42 351652671 Ed. 02 Menu de programmation étendu Dans le menu de programmation étendu, vous pouvez configurer tous les paramètres de l'appareil pour l'adapter aux besoins de votre installation. Pour y accéder, appuyer sur la touche SET pendant 6 secondes. IMPORTANT : si la fonction du mot de passe a été configurée comme blocage du clavier (b10 = 2), ou comme blocage de l'accès aux paramètres (b10 = 1) lors d'une tentative d'accès à...
  • Page 43 351652671 Ed. 02 Paramètres Réglage et contrôle Description Valeurs Min. Déf. Max. SP Réglage de température (Set Point) ºC/ºF -50 0,0 99 C0 Calibrage de la sonde 1 (offset) ºC/ºF -20,0 0,0 20,0 C1 Différentiel de la sonde 1 (hystérésis) ºC/ºF 0,1 2,0 20,0 Blocage supérieur du point de consigne...
  • Page 44 351652671 Ed. 02 Dégivrage Description Valeurs Min. Déf. Max. d0 Fréquence de dégivrage (délai entre 2 démarrages) d1 Durée maximale du dégivrage (0 = dégivrage désactivé) min. Type de message pendant le dégivrage : 0 = affiche la température réelle ; 1 = affiche la température au début du dégivrage ;...
  • Page 45 351652671 Ed. 02 Détendeur Description Valeurs Min. Déf. Max. Type de détendeur : 0 = solénoïde + détendeur thermostatique 1 = DE type PWM 2 = DE type stepper Sh Set Point de surchauffe Type de gaz réfrigérant : 0= R-404A, 1= R-134A, 2= R-407A, 3= R-407F, 4= R-410A, 5= R-450A, 6= R-513A, 7= R-744, 8= R-449A, 9= R-290, 10= R-32, 11= R-448A, 12=R1234ze, 13=R23, 14=R717, 15=R407C, 16=R1234yf, 17=R22, 18=R454C, 19=R455A, 20=R507A, 21=R515B, 22=R452A, 23=R452B, 24=R454A...
  • Page 46 351652671 Ed. 02 Alarmes Description Valeurs Min. Déf. Max. A0 Configuration des alarmes de température 0 = relative au SP 1 = absolue A1 Alarme de maximum sur sonde 1 (doit être supérieur au SP) ºC/ºF A2 99,0 99,0 A2 Alarme de minimum sur sonde 1 (doit être inférieur au SP) ºC/ºF -50 -50 A1 Retard d'alarmes de température à...
  • Page 47 351652671 Ed. 02 Configuration de base Description Valeurs Min. Déf. Max. b00 Retard de toutes les fonctions lors de la réception d'alimentation électrique min. b01 Temporisation éclairage chambre min. Fonction du mot de passe (password) 0 = inactif 1 = blocage de l’accès aux paramètres ; 2 = blocage du clavier Mot de passe (password) b20 Adresse MODBUS Vitesse de communication : 0 = 9 600 bps 1 = 19 200 bps...
  • Page 48 351652671 Ed. 02 Entrées et sorties Description Valeurs Min. Déf. Max. I60 Unités de pression : 0 = bar, 1 = Psi Type de capteur de pression (S6) : 0 = désactivé, 1 = 4-20 mA, 2 = 0-5 V, 3 = 0,5-4,5 V, 4 = 0-10 V, 5 = 1-5 V I62 Valeur minimale de la sonde de pression (4 mA, 0 V, 0,5 V, 1 V) I63 Valeur maximale de la sonde de pression (20 mA, 5 V, 4,5 V, 10 V)
  • Page 49 Précision thermométrique ..........................± 1 ºC Tolérance des sondes (NTC/Pt1000) à 25 ºC .....................± 0,4 ºC Entrées S1 à S4 ..................Sonde NTC AKO-14901 ou sonde Pt1000 Entrée S5 ................Sonde NTC AKO-14950 / 14950-8 ou sonde Pt1000 Température ambiante de travail ......................-10 à 40 ºC Température ambiante de stockage ....................-30 ºC à...
  • Page 50 351652671 Ed. 02...
  • Page 51 351652671 Ed. 02...
  • Page 52 AKO ELECTROMECÁNICA , S.A.L. Avda. Roquetes, 30-38 08812 • Sant Pere de Ribes. Barcelona • Spain www.ako.com Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los descritos en nuestras Hojas Técnicas. Información actualizada en nuestra web.